Plan Review Notes For Permit 03031677 |
Permit Number |
03031677 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-31 00:00:00 | DENIED; | | PAGE 2OF 10 PLUMBING RISER DIAGRAM DOES | | NOT MATCH FLOOR PLAN. CABANA BATH AND | | BAR SINK MISSING. 1/2 BATH LAV DOWN | | STREAM OF W/C. MASTER BATH LAVS CANNOT | | BE INSTALLED ON SAME STACK. KITCHEN SINK | | SINK SHOULD HAVE A MECHANICAL VENT, NO | | WALL FOR STACK. UTILITY SINK AND W/M ARE | | ON DIFFERENT WALL. UP STAIR BATH NEED | | TWO STACKS FOR LAVS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|