2003-04-03 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE MISSING SD ON LOWER
 LEVEL AT BOTTOM OF STAIRS. NFPA-72
 8-1.4.2
  
 2)NOTE: PLEASE CLARIFY/VERIFY KW RATING
 FOR TANKLESS WATER HEATERS SHOWN AT 800W
 `S. PLEASE NOTE 800W TLWH ARE NOT A
 TYP SIZE FOR A HOUSE THIS SIZE.
 PLEASE SUBMIT SPECS ON UNITS BEING
 INSTALLED AND REDO LOAD CALCULATIONS.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE,
 MANY ITEMS ARE SHOWN AS 2-POLE AND ONLY
 TAKE ONE SPACE IN PANEL AND ARE LABELED
 FOR 1-POLE??33,34,35 ,,,
  
 4)NOTE: PLEASE SEE LOAD CALCUALTIONS,
 LOAD FOR AHU/HEAT ONLY SHOWS ONE OF THE
 10KW UNITS IN LOAD CALCS??
 PLEASE ADJUST PER NEC 220
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 PER 210-12
  
 6)NOTE: PLEASE VERIFY LOCATION OF TKLWH
 ON SECOND FLOOR, BEHIND BEDROOM DOOR
 IN BEDROOM #4??
  
 7)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 ALL MAINS/PANELS/BRKRS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. 110-9
 215-5
  
 8)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE. PLEASE SEE 210-52
 C-1. 12" OF COUNTER/WALL SPACE.
  
 9)NOTE: PLEASE SEE 210-52 FOR RECEPTS
 MISSING. 2',6',12' RULE.
  
 10)NOTE: PLEASE CORRELATE PLAN AND PANEL
 SCHEDULE. PLAN SHOWS POOL PUMP AND
 IRRIGATION PUMP AT 220V AND PANEL SCH
 SHOWS 120V??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  