2003-04-03 00:00:00 | ************ UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE MISSING SD ON LOWER |
| LEVEL AT BOTTOM OF STAIRS. NFPA-72 |
| 8-1.4.2 |
| |
| 2)NOTE: PLEASE CLARIFY/VERIFY KW RATING |
| FOR TANKLESS WATER HEATERS SHOWN AT 800W |
| `S. PLEASE NOTE 800W TLWH ARE NOT A |
| TYP SIZE FOR A HOUSE THIS SIZE. |
| PLEASE SUBMIT SPECS ON UNITS BEING |
| INSTALLED AND REDO LOAD CALCULATIONS. |
| |
| 3)NOTE: PLEASE SEE PANEL SCHEDULE, |
| MANY ITEMS ARE SHOWN AS 2-POLE AND ONLY |
| TAKE ONE SPACE IN PANEL AND ARE LABELED |
| FOR 1-POLE??33,34,35 ,,, |
| |
| 4)NOTE: PLEASE SEE LOAD CALCUALTIONS, |
| LOAD FOR AHU/HEAT ONLY SHOWS ONE OF THE |
| 10KW UNITS IN LOAD CALCS?? |
| PLEASE ADJUST PER NEC 220 |
| |
| 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTED CIRCUITS ON PANEL SCHEDULE |
| PER 210-12 |
| |
| 6)NOTE: PLEASE VERIFY LOCATION OF TKLWH |
| ON SECOND FLOOR, BEHIND BEDROOM DOOR |
| IN BEDROOM #4?? |
| |
| 7)NOTE: PLEASE SUBMIT AIC RATING FOR |
| NEW SERVICE EQUIPMENT BEING INSTALLED. |
| ALL MAINS/PANELS/BRKRS ARE TO BE RATED |
| FOR THE AVAILABLE FAULT CURRENT. 110-9 |
| 215-5 |
| |
| 8)NOTE: PLEASE SEE MISSING RECEPT FOR |
| KITCHEN COUNTERSPACE. PLEASE SEE 210-52 |
| C-1. 12" OF COUNTER/WALL SPACE. |
| |
| 9)NOTE: PLEASE SEE 210-52 FOR RECEPTS |
| MISSING. 2',6',12' RULE. |
| |
| 10)NOTE: PLEASE CORRELATE PLAN AND PANEL |
| SCHEDULE. PLAN SHOWS POOL PUMP AND |
| IRRIGATION PUMP AT 220V AND PANEL SCH |
| SHOWS 120V?? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |