2003-04-28 00:00:00 | BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) THE PERCENTAGE OF WALL AREA ALLOWED |
| TO BE OPENINGS BY FBC TABLE 600 IS |
| EXCEEDED AT THE FIRST AND SECOND FLOORS |
| ON THE RIGHT ELEVATION. |
| |
| 4) THE UPLIFT VALUE LISTED IN THE |
| CONNECTOR SCHEDULE ON PAGE 5 FOR THE (2) |
| HETA 20 ANCHORS (MARK C) IS INCORRECT. |
| ACCORDING TO THE 2003 SIMPSON CATALOG |
| THE UPLIFT VALUE FOR A DOUBLE HETA 20 IS |
| 2035# FOR A ONE PLY TRUSS AND 2500# FOR |
| TWO OR THREE PLY TRUSSES. |
| |
| 5) THE WALL LEGEND ON PAGE 6 SPECIFIES |
| THE TOP OF THE CROSS MARKED WALLS TO BE |
| 10 FEET ABOVE FINISH FLOOR. THESE WALLS |
| ARE 12 FEET ACCORDING TO THE ELEVATIONS. |
| |
| 6) SPECIFY ON THE PLANS THE GUARDRAIL |
| HEIGHT, THE SPACING OF THE INTERMEDIATE |
| RAILS AND THE BOTTOM RAIL AT THE BALCONY |
| SEE FBC 1015.3 AND 1026.5.1. SUBMIT |
| SHOP DRAWINGS PRIOR TO INSTALLATION. |
| |
| 7) THE STAIR WINDERS ARE REQUIRED TO |
| HAVE A MINIMUM TREAD DEPTH OF 6 INCHES |
| AT THE NARROW EDGE AND HAVE A MINIMUM |
| TREAD DEPTH OF 11 INCHES AT A POINT 12 |
| INCHES FROM THE NARROW EDGE. SEE |
| FBC 1007.8.1 |
| |
| 9) THE WALL SECTION ON PAGE 4 SPECIFIES |
| R-30 INSULATION IN THE 2X6 WALL. PLEASE |
| CORRECT. |
| |
| 10) INDICATE THE LOCATIONS AND SIZES OF |
| THE ATTIC ACCESS OPENINGS AT THE GARAGE |
| AND THE SECOND STORY. SEE FBC 2309.6. |
| |
| 11) THE WALL SECTION ON PAGE 4 SPECIFIES |
| A VENTED ALUMINUM SOFFIT. SUBMIT THE |
| PRODUCT APPROVALS AND MANUFACTURER'S |
| SPECIFICATIONS FOR THIS ITEM. |
| |
| 12) PLEASE CLARIFY THE 1/4 NAILER AND |
| 1/4 WINDOW BUCK LISTED ON THE WALL |
| SECTION ON PAGE 4. |
| |
| 13) INDICATE FIREBLOCKING ON THE WALL |
| SECTIONS WHERE THE FURRED SPACE OF WALL |
| AND CEILING MEET PER FBC 2305.1. THE |
| CONCEALED SPACES BETWEEN THE STAIR |
| STRINGERS ARE REQUIRED TO BE FIREBLOCKED |
| AT THE TOP AND BOTTOM OF RUNS PER FBC |
| 2305.1.4. |
| |
| 14) INDICATE THE LOCATION AND MATERIAL |
| THAT WILL BE USED TO TO PROVIDE THE |
| DRAFTSTOPPING REQUIRED BY FBC 2305.2.2 |
| TO DIVIDE THE FLOOR/CEILING ASSEMBLY |
| INTO AREAS NO GREATER THAN 500 SQFT. |
| SEE FBC 2305.2.6 FOR APPROVED MATERIALS. |
| |
| 15) PROVIDE A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. THE |
| SBCCI REPORT (PRODUCT APPROVAL) THAT WAS |
| SUBMITTED FOR STORM PANELS IS EXPIRED. |
| SUBMIT CURRENT REPORT. |
| |
| 16) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL MULLIONS |
| - GLASS BLOCK |
| - SINGLE OUTSWING DOORS AT THE GARAGE |
| AND CABANA BATH |
| - THE SEVEN PAGES OF DRAWINGS THAT ARE |
| PART OF THE SINGLE HUNG WINDOW NOA |
| - FIXED GLASS EYEBROW WINDOWS |
| - FIXED GLASS TRANSOM ABOVE (3) 26 SH |
| WINDOWS AT LIVING ROOM ( THE PRODUCT |
| APPROVAL SUBMITTED DOES NOT INCLUDE |
| NINE FEET PLUS WIDE WINDOWS OR EYEBROW |
| WINDOWS) |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |