Plan Review Notes For Permit 03031586 |
Permit Number |
03031586 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-11 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-RE-SUBMIT STORM SHUTTERS INFORMATION | | WITH UPDATED SBCCI PRODUCT APPROVAL | | REPORT THAT MATCHES ENGINEERED DWGS. | | CHECK THE DESIGN PRESSURES AND MAX/MIN | | PANEL SPAN AND REVISE THE INSTALLATION | | SCHEDULE AS REQUIRED. | | 2-RE-SUBMIT ENERGY CALCULATIONS WITH | | ENGINEER'S ORIGINAL SIGNATURE & SEAL. | | CHAPTER 471 FLORIDA STATUTES AND SEC. | | 103.0 CHAPTER 13 FBC 2001. | | 3-SPECIFY DETAIL AT TOP OF WOOD COLUMN | | BY THE STAIRS. SEE SHEET S-1.SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
|