2003-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SOME CUT SECTIONS MISSING
 1-1/4" GALV REQUIRED INTO BLDG & UP 1ST
 15 FEET. - 1" REQUIRED FOR RANGE DROP.
 2. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. ROOM WITH DRYER &
 WATER A CONFINED SPACE.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4) FIREPLACE SHOWS 40,000 BTU'S AND CUT
 SHEET SHOWS 22,000 BTU'S MAXIMUM. PLEASE
 CLAIRFY
  