2003-03-25 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. SOME CUT SECTIONS MISSING | | 1-1/4" GALV REQUIRED INTO BLDG & UP 1ST | | 15 FEET. - 1" REQUIRED FOR RANGE DROP. | | 2. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | GAS CODE SECTION 304. ROOM WITH DRYER & | | WATER A CONFINED SPACE. | | 3. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | 4) FIREPLACE SHOWS 40,000 BTU'S AND CUT | | SHEET SHOWS 22,000 BTU'S MAXIMUM. PLEASE | | CLAIRFY | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|