Plan Review Notes
Plan Review Notes For Permit 03031456
Permit Number 03031456
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-02 00:00:00************ NOTES/REDLINED***********
  
 PLEASE SEE PLANS, THERE ARE MISSING ITEM
 -S REDLINED.
  
 1)NOTE: PLEASE MOVE SD INSIDE MASTER
 BEDROOM.NFPA-72 8-1.4.2
  
 2)NOTE: PLEASE SEE 210-52C-1 FOR COUNTER
 TOP OUTLET SPACING IN KITCHEN. MISSING
 ONE.
  
 3)NOTE: PLEASE SEE MISSING RECEPT PER
 210-52 W/IN 6' OF DOORWAY IN BREAKFAST
 AREA.
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL. SIZE PER 250-122
  
 PLEASE REVISE PLANS BEFORE ROUGH.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372