2003-04-02 00:00:00*************NOTES REDLINED ************
  
 PLEASE NOTE, THE FOLLOWING ARE ITEMS
 MISSING ON PLANS.
  
 1)NOTE: PLEASE MOVE SD INTO MASTER
 BEDROOM. NFPA-72 8-1.4.2
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISCONNECT
 TO PANEL. PER 250-122
  
 3)NOTE: PLEASE SEE MISSING COUNTERSPACE
 RECEPT PER 210-52-C-1
  
 4)NOTE: PLEASE SEE MISSING RECEPT IN
 BREAKFAST AREA W/IN 6' OF DOOR. 210-52
  
 PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  