Notes |
Date |
Text |
2003-04-02 00:00:00 | *************NOTES REDLINED ************ | | | | PLEASE NOTE, THE FOLLOWING ARE ITEMS | | MISSING ON PLANS. | | | | 1)NOTE: PLEASE MOVE SD INTO MASTER | | BEDROOM. NFPA-72 8-1.4.2 | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | GROUNDING CONDUCTOR FROM MAIN DISCONNECT | | TO PANEL. PER 250-122 | | | | 3)NOTE: PLEASE SEE MISSING COUNTERSPACE | | RECEPT PER 210-52-C-1 | | | | 4)NOTE: PLEASE SEE MISSING RECEPT IN | | BREAKFAST AREA W/IN 6' OF DOOR. 210-52 | | | | PLEASE REVISE AND SUBMIT FOR REVIEW | | BEFORE ROUGH. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|