Plan Review Notes
Plan Review Notes For Permit 03031260
Permit Number 03031260
Review Stop P
Sequence Number 1
Notes
Date Text
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92, AND NSPI-5. (ADD TO
 NOTES)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 VACUUM NOT FOUND ON POOL LAY OUT, BUT
 ITS CALLED FOR IN GENERAL SPECIFICATIONS
 3) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (GIVE DETAIL)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) GENERAL NOTES #5 NOT APPLICABLE.
 PLEASE UPDATE TO CORRECT FBC-2001
 6) 50% OF ONE DETAIL SHEET IS BLANK.
 PLEASE REVIEW PLANS PRIOR TO SIGNING &
 SEALING.
  
 REVIEW BY KEN STEVENS