Plan Review Notes For Permit 03031260 |
Permit Number |
03031260 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-24 00:00:00 | *************** UNSAT ************* | | | | 1)NOTE: PLEASE SHOW TIME CLOCK AS REQ`D | | UNDER FBC. | | | | 2)NOTE: PLEASE SEE WHERE THERE IS ONLY | | HALF OF ONE SHEETS SUBMITTED AND YET | | IT IS SIGNED AND SEALED BY ENGINEER? | | PLEASE ALSO SUMIT TITLE BLOCK INFORMAT- | | -ION AS SET FORTH UNDER FS AND FAC | | 61G15-23.002. MUST ALSO CONTAIN LIC #. | | PLEASE SEE SHEET MISSING TITLE BLOCK. | | | | 3)NOTE: PLEASE SHOW HOW HEATER IS BEING | | CONNECTED. NOT SHOWN ON RISER. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|