Plan Review Notes
Plan Review Notes For Permit 03031105
Permit Number 03031105
Review Stop P
Sequence Number 4
Notes
Date Text
2003-07-11 00:00:00PASSED/PROVISO
  
 FILLMASTER FILTER NOT APPROVED. FILTER
 SHALL BE NSP APPROVED AND LABELED PER
 SECTION 303.4 - WILL SUBMIT MODEL THAT
 IS LABELED PRIOR TO ROUGH INSPECTION.
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN CEILING.