Plan Review Notes For Permit 03031105 |
Permit Number |
03031105 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-07-09 00:00:00 | ********** NOTES REDLINED ********* | | | | PLEASE SEE NOTE REDLINED ON RISER | | DIAGRAM. NO MORE THAN 8' OF UNPROTECTED | | CONDUCTOR INSIDE BLDG PER LOCAL | | AMENDMENTS 210-70 | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS | | FROM SETS. | | | | MDP PANEL SCHEDULEON E-11 STILL SHOWS | | MLO. | | | | PLEASE REVISE PLANS BEFORE ROUGH | | ELECTRICAL INSPECTION IS CALLED IN. | | | | IF THERE ARE ANY QUESTINOS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|