Plan Review Notes For Permit 03031105 |
Permit Number |
03031105 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-06-14 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | FOLLOWING COMMENTS NOT ADDRESSED FROM | | PRIVIOUS REVIEW. FOR CLAIRTY THE COMMENT | | NUMBER FROM FIRST REVIEW WILL BE USED. | | | | 4) SHT P-1, #13 FILTER SHALL COMPLY WITH | | NSF STANDARD. MANUF. INFO REQUIRED. | | 7) (IN PART) WATER HAMMER ARRESTORS REQ- | | UIRED BY SEC 406.9 SHALL BE LOCATED NEAR | | THE FIXTURE IN AN "EFFICTIVE RANGE" NOT | | IN THE CEILING AT THE TOP OF THE DROP. | | PDI-WH 201 & MANUF. INSTALLATION | | INSTRUCTIONS. | | | | NEW COMMENT. | | *********WHEN RESUBMITTING PLANS******** | | PLEASE CLEARLY INDICATE THE REVISION AND | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | THE PLANS WHEN RESUBMITTING PLANS. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|