Plan Review Notes For Permit 03031105
Permit Number 03031105
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 FOLLOWING COMMENTS NOT ADDRESSED FROM
 PRIVIOUS REVIEW. FOR CLAIRTY THE COMMENT
 NUMBER FROM FIRST REVIEW WILL BE USED.
  
 4) SHT P-1, #13 FILTER SHALL COMPLY WITH
 NSF STANDARD. MANUF. INFO REQUIRED.
 7) (IN PART) WATER HAMMER ARRESTORS REQ-
 UIRED BY SEC 406.9 SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFICTIVE RANGE" NOT
 IN THE CEILING AT THE TOP OF THE DROP.
 PDI-WH 201 & MANUF. INSTALLATION
 INSTRUCTIONS.
  
 NEW COMMENT.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.