Date Text
2003-05-30 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING COMMENTS FROM
 THE LAST REVIEW THAT WERE ONLY
 PARTIALLY ADDRESSED OR NOT
 SATIFACTORILY ADDRESSED.
  
 1} THE PANEL SCHEDULES ARE STILL LISTING
 MLO & MAIN,AND NOW PANELS "C" & "P"
 LIST MCB.IF THE PANEL RATING IN AMPS IS
 225 OR 100,IT SHOULD NOT BE LISTED AS
 IF THAT WERE THE MAIN BREAKER
 SIZE.PLEASE CLARIFY ALL PANEL
 DESIGNATIONS WITH CONSISTENCY.
  
 2} THERE ARE STILL SEVERAL EXIT &
 EMERGENCY LIGHTS ON CIRCUIT A-20(SHEET
 E-2). THIS IS IN VIOLATION OF ARTICLE
 700-12(E).
  
 PLEASE CORRECT AND RESUBMIT FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718