2003-05-29 00:00:00THE DELTA FIRE SPRINKLER PLANS DO NOT
 HAVE COMPLETE DESIGN INFORMATION AND
 WERE NOT PREPARED BY AN ENGINEER.SEE
 FBC 104.2 AND THE FL ADMINISTRATIVE
 CODE CHAPTERS 61G15-31 AND 61G15-32.
  
 THE PLANS DO NOT SHOW THE DRAFTSTOPPING
 IN THE EXTERIOR WOOD TRUSS CANOPY IN
 ACCORDANCE WITH FBC 2305.2.4.
  
 THE HORTON AUTOMATIC NOA 03-0306.05 IS
 MISSING PAGES.NOA 00-0512.12 IS
 EXPIRED AND ILLEGIBLE.
  
 THE SW FLEMING NOA 97-0327.01 IS
 EXPIREDNOA 01-0129.09 IS MISSING PAGES
 AND IS ILLEGIBLE.
  
 NOA 00-0508.01 HAS THE WRONG DRAWINGS
 ATTACHED TO IT.