Plan Review Notes For Permit 03031105 |
Permit Number |
03031105 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-05-29 00:00:00 | THE DELTA FIRE SPRINKLER PLANS DO NOT | | HAVE COMPLETE DESIGN INFORMATION AND | | WERE NOT PREPARED BY AN ENGINEER.SEE | | FBC 104.2 AND THE FL ADMINISTRATIVE | | CODE CHAPTERS 61G15-31 AND 61G15-32. | | | | THE PLANS DO NOT SHOW THE DRAFTSTOPPING | | IN THE EXTERIOR WOOD TRUSS CANOPY IN | | ACCORDANCE WITH FBC 2305.2.4. | | | | THE HORTON AUTOMATIC NOA 03-0306.05 IS | | MISSING PAGES.NOA 00-0512.12 IS | | EXPIRED AND ILLEGIBLE. | | | | THE SW FLEMING NOA 97-0327.01 IS | | EXPIREDNOA 01-0129.09 IS MISSING PAGES | | AND IS ILLEGIBLE. | | | | NOA 00-0508.01 HAS THE WRONG DRAWINGS | | ATTACHED TO IT. |
|