Plan Review Notes
Plan Review Notes For Permit 03031105
Permit Number 03031105
Review Stop P
Sequence Number 1
Notes
Date Text
2003-03-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A2.2 PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SEC'S 1106 & 1107. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, (1106.4), INCLUDING
 PARAPET, (1106.5). SHOW AREA OF ROOFS
 THAT DRAIN ON TO ROOF FROM ABOVE.
 INDICATE SQUARE FOOTAGE DRAINED BY EACH.
 2) SHT 2.2 INDICATE PITCH OF GUTTERS PER
 TABLE 1106.6 AND SHOW SQUARE FOOTAGE
 DRAINED FROM EACH ROOF AREA TO GUTTER.
 3) SHT A2.2 INDICATES 24"X16" SCUPPERS
 AND OVERFLOW SCUPPERS. IT SAYS TYPICAL
 OF 5, BUT ONLY 4 ARE SHOWN. PLEASE
 CLAIRFY.
 4) SHT P-1 #13 FILTER SHALL COMPLY WITH
 NSF STANDARD. MANUF. INFO. REQUIRED.
 5) SHT P-1 #'S 15 & 19, FLOOR DRAINS ARE
 NOT APPROVED FOR INDIRECT WASTE. ALL
 INDIRECT WASTE SHALL DRAIN TO FLOOR SINK
 SECTION 802.3
 6) SHT P-3 DETAILS #3 & 6, FLOOR SINKS
 REQUIRED. SECTION 802.3
 7) SHT P-4 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS REQUIRED BY 406.9, (AT QUICK
 CLOSING VALVES), SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 AT THE TOP OF THE DROP IN THE CEILING.
 PDI-WH 201 & MANUF. INSTALLATION INSTR.
 8) IRRIGATION PERMIT REQUIRED. PLUMBING
 CONTRACTOR SHALL TIE INTO WATER SERVICE
 AND SUPPLY SHUT OFF VALVE FOR IRRIGATION
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377