2003-03-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHT A2.2 PROVIDE CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS PER |
| SEC'S 1106 & 1107. SHOW 1/2 AREA OF ALL |
| VERTICAL WALLS, (1106.4), INCLUDING |
| PARAPET, (1106.5). SHOW AREA OF ROOFS |
| THAT DRAIN ON TO ROOF FROM ABOVE. |
| INDICATE SQUARE FOOTAGE DRAINED BY EACH. |
| 2) SHT 2.2 INDICATE PITCH OF GUTTERS PER |
| TABLE 1106.6 AND SHOW SQUARE FOOTAGE |
| DRAINED FROM EACH ROOF AREA TO GUTTER. |
| 3) SHT A2.2 INDICATES 24"X16" SCUPPERS |
| AND OVERFLOW SCUPPERS. IT SAYS TYPICAL |
| OF 5, BUT ONLY 4 ARE SHOWN. PLEASE |
| CLAIRFY. |
| 4) SHT P-1 #13 FILTER SHALL COMPLY WITH |
| NSF STANDARD. MANUF. INFO. REQUIRED. |
| 5) SHT P-1 #'S 15 & 19, FLOOR DRAINS ARE |
| NOT APPROVED FOR INDIRECT WASTE. ALL |
| INDIRECT WASTE SHALL DRAIN TO FLOOR SINK |
| SECTION 802.3 |
| 6) SHT P-3 DETAILS #3 & 6, FLOOR SINKS |
| REQUIRED. SECTION 802.3 |
| 7) SHT P-4 WATER RISER DIAGRAM, AIR |
| CHAMBERS ARE NOT APPROVED. WATER HAMMER |
| ARRESTORS REQUIRED BY 406.9, (AT QUICK |
| CLOSING VALVES), SHALL BE LOCATED NEAR |
| THE FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| AT THE TOP OF THE DROP IN THE CEILING. |
| PDI-WH 201 & MANUF. INSTALLATION INSTR. |
| 8) IRRIGATION PERMIT REQUIRED. PLUMBING |
| CONTRACTOR SHALL TIE INTO WATER SERVICE |
| AND SUPPLY SHUT OFF VALVE FOR IRRIGATION |
| |