Plan Review Notes
Plan Review Notes For Permit 03031105
Permit Number 03031105
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-04-04 00:00:001) THE BUILDING IS LOCATED IN THE
 CITY FIRE LIMITS. CERTAIN RESTRICTIONS
 APPLY. PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 2) ELECTRONIC SWITCHES ARE REQUIRED
 ON THE FIRE LINE BACKFLOW DEVICE.
  
 3) THE AUTOMATIC DOORS SHALL COMPLY
 WITH NFPA 101, THE LIFE SAFETY CODE,
 2000 EDITION, SECTION 7.
  
 4) PLEASE OBTAIN YOUR KNOX-BOX
 APPLICATION FROM THIS OFFICE SO YOU
 CAN ODER IT.
  
 5) WOOD NOTED ON EXTERIOR. AGAIN
 CERTAIN RESTRICTIONS APPLY IN THE
 FIRE LIMITS.
  
 6) THE BUILDING ADDRESS IS REQUIRED
 ON THE PROPER ELEVATION.
  
 7) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR HANDRAILS.
  
 8) HOW DOES THE MONUMENT SIGN NOT
 INTERFERE WITH ACCESS TO THE PROPOSED
 FIRE HYDRANT.
  
 9) SECURITY DEVICES INSTALLED SHALL
 NOT INTERFERE WITH ANY EGRESS FROM
 THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910