2003-03-24 00:00:00************* UNSAT ********************
  
  
 1)NOTE: PLEASE SEE GENERAL NOTE FOR
 AIC RATINGS. IT IS NOTED THAT "PANELS"
 ARE TO BE 65K SERIES RATED, PLEASE
 CLARIFY IF THIS IF FOR MAIN DISC ALSO.?
 110-9
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES. PLEASE SEE RISER
 SHOWS PANELS "C" AND "P" AS 225A AND
 PANEL SCHEDULES SHOW THEM AS 100A.
 PLEASE ALSO CLARIFY PANELS. THEY ARE
 ALL SHOWN AS MLO AND MCB? P RISER SHOWS
 PANELS AS BEING MLO.?
  
 3)NOTE: PLEASE SHOW CIRCUITING FOR
 EM/EXT LTS PER 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  