Plan Review Notes
Plan Review Notes For Permit 03031011
Permit Number 03031011
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-11 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-RE-SUBMIT ENERGY CALCULATIONS WITH THE
 ENGINEER'S ORIGINAL SIGNATURE & SEAL.
 CHAPTER 471 FLORIDA STATUTES AND SEC.
 103.0 CHAPTER 13 FBC 2001.
 2-RE-SUBMIT STORM SHUTTERS INFORMATION
 WITH UPDATED SBCCI PRODUCT APPROVAL
 THAT MATCHES ENGINEERED DRAWINGS AND
 CHECK DESIGN PRESSURES AND PANEL MAX.
 MIN. SPAN ON ENGINEERED DRAWINGS AND
 REVISE INSTALLATION SCHEDULE AS REQ'D.
 3-CLARIFY/REVISE DETAIL S-26 FOR COLUMN
 LOCATED BETWEEN GARAGE AND KITCHEN.
 SEE 2ND FLOOR FRAMING PLAN FOR ACTUAL
 FRAMING CONDITIONS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION.