Plan Review Notes
Plan Review Notes For Permit 03031002
Permit Number 03031002
Review Stop M
Sequence Number 2
Notes
Date Text
2003-05-05 00:00:00PROVISO:
  
 1.PROVIDE OUTSIDE AIR CALCS AS PER
 2001 FBC(M) 402.2 (NATURAL) OR TABLE
 403.3, ON JOBSITE FOR ROUGH INSPECTION.
  
 2.CLARIFY ENERGY & MANUAL J CALCS ON
 SIZING OF A/C EQUIPMENT INDICATES A 4
 TON UNIT AND PLAN SCHEDULE ON PLAN SHEET
 M-1 SHOW A 5 TON UNIT.
  
 3.FAN SHUTDOWN REQUIRED AT FINAL
 INSPECTION AS PER 2001 FBC(M) 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.