2003-03-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE PLANS TO COMPLY WITH
 THE FOLLOWING.
  
 1} THE FEEDER FROM THE MAIN TO PANEL "A"
 IS INCORRECT FOR 200 AMPS.
  
 2} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 4} PLEASE NOTE THAT THE RECEPTACLE
 SPACING IN THE DINING ROOM DOES NOT
 COMPLY WITH 210-52(A)(1).
  
 5} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  