2003-04-10 00:00:00BUILDING REVIEW CHECKLIST:
 1-EXTERIOR REAR ELEVATION EXCEEDS THE
 MAXIMUM OPENINGS ALLOWED BY TABLE 600
 FBC 2001. REVISE AS REQUIRED.
 2-RE-SUBMIT ENERGY CALCULATIONS WITH
 ENGINEER'S ORIGINAL SIGNATURE AND SEAL
 AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES AND SECTION 103.0 CHAPTER 13
 FBC 2001.
 3-RE-SUBMIT STORM PANELS INFORMATION W/
 UPDATED SBCCI PRODUCT APPROVAL THAT
 MATCHES ENGINEERED DRAWINGS. ALSO,
 REVISE INSTALLATION SCHEDULE SHOWING
 CORRECT DESIGN PRESSURES AND MAX/MIN.
 PANEL SPANS AS SHOWN ON ENGINEERED
 DRAWINGS.SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-REVISE DETAIL S-26. IT DOESN'T APPLY.
 SEE 2ND FL. FRAMING PLAN AND PROVIDE
 COMPLETE DETAIL SHOWING ACTUAL FRAMING
 CONDITIONS AND CONNECTOR FOR COLUMN
 LOCATED BETWEEN GARAGE AND KITCHEN.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.