Plan Review Notes For Permit 03030866 |
Permit Number |
03030866 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-10 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1-EXTERIOR REAR ELEVATION EXCEEDS THE | | MAXIMUM OPENINGS ALLOWED BY TABLE 600 | | FBC 2001. REVISE AS REQUIRED. | | 2-RE-SUBMIT ENERGY CALCULATIONS WITH | | ENGINEER'S ORIGINAL SIGNATURE AND SEAL | | AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTES AND SECTION 103.0 CHAPTER 13 | | FBC 2001. | | 3-RE-SUBMIT STORM PANELS INFORMATION W/ | | UPDATED SBCCI PRODUCT APPROVAL THAT | | MATCHES ENGINEERED DRAWINGS. ALSO, | | REVISE INSTALLATION SCHEDULE SHOWING | | CORRECT DESIGN PRESSURES AND MAX/MIN. | | PANEL SPANS AS SHOWN ON ENGINEERED | | DRAWINGS.SECTION 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 4-REVISE DETAIL S-26. IT DOESN'T APPLY. | | SEE 2ND FL. FRAMING PLAN AND PROVIDE | | COMPLETE DETAIL SHOWING ACTUAL FRAMING | | CONDITIONS AND CONNECTOR FOR COLUMN | | LOCATED BETWEEN GARAGE AND KITCHEN. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|