Plan Review Notes
Plan Review Notes For Permit 03030863
Permit Number 03030863
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-10 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-RE-SUBMIT ENERGY CALCULATIONS WITH
 ENGINEER'S ORIGINAL SIGNATURE & SEAL.
 CHAPTER 471 FLORIDA STATUTES AND SEC.
 103.0 CHAPTER 13 FBC 2001.
 2-RE-SUBMIT STORM PANELS INFORMATION W/
 UPDATED SBCCI REPORT THAT MATCHES THE
 ENGINEERED DRAWINGS AND REVISE THE
 INSTALLATION SCHEDULE. CHECK DESIGN
 PRESSURES AND PANEL MAX/MIN SPAN.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-REVISE DETAIL S-26. IT DOESN'T APPLY.
 SEE 2ND FLOOR FRAMING PLAN FOR ACTUAL
 FRAMING CONDITIONS AND CONNECTOR THAT
 IS REQUIRED FOR COLUMN LOCATED BET.
 GARAGE AND KITCHEN. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.