Plan Review Notes
Plan Review Notes For Permit 03030854
Permit Number 03030854
Review Stop B
Sequence Number 3
Notes
Date Text
2003-05-14 00:00:00CHECKLIST FOR ARCHITECT'S APPROVAL
 LETTER REGARDING WINDOWS:
 1-WHAT IS A "34HS" WINDOW? IS THIS A
 HORIZONTAL SLIDER?. SEE PLANS THERE
 THERE ARE NOT HORIZONTAL SLIDERS
 SPECIFIED ON THE WINDOW SCHEDULE.
 2-WHAT ARE THE "ALL FBC DESIGN REQUIRE-
 MENTS" BEEN REVIEWED FOR?. WIND LOAD?,
 EGRESS?.
 3-MY ORIGINAL COMMENT WAS THAT WINDOW
 "F" 34SH DIDN'T MEET THE MINIMUM 24"
 CLEAR HEIGHT OPENING REQUIRED BY SEC.
 1005.4 FBC 2001 FOR BEDROOMS.
 THE APPROVAL LETTER SUBMITTED BY THE
 ARCHITECT DOESN'T ADDRESS THIS ISSUE.
 THE WINDOW SCHEDULE IS THE ONE THAT
 NEEDS TO BE REVISED.