Plan Review Notes For Permit 03030854 |
Permit Number |
03030854 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-05-14 00:00:00 | CHECKLIST FOR ARCHITECT'S APPROVAL | | LETTER REGARDING WINDOWS: | | 1-WHAT IS A "34HS" WINDOW? IS THIS A | | HORIZONTAL SLIDER?. SEE PLANS THERE | | THERE ARE NOT HORIZONTAL SLIDERS | | SPECIFIED ON THE WINDOW SCHEDULE. | | 2-WHAT ARE THE "ALL FBC DESIGN REQUIRE- | | MENTS" BEEN REVIEWED FOR?. WIND LOAD?, | | EGRESS?. | | 3-MY ORIGINAL COMMENT WAS THAT WINDOW | | "F" 34SH DIDN'T MEET THE MINIMUM 24" | | CLEAR HEIGHT OPENING REQUIRED BY SEC. | | 1005.4 FBC 2001 FOR BEDROOMS. | | THE APPROVAL LETTER SUBMITTED BY THE | | ARCHITECT DOESN'T ADDRESS THIS ISSUE. | | THE WINDOW SCHEDULE IS THE ONE THAT | | NEEDS TO BE REVISED. |
|