Plan Review Notes For Permit 03030708 |
Permit Number |
03030708 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-07-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | FLORIDA STATUTES | | | | 1) FROM PREVIOUS REVIEWS: PER TABLE | | 403.1 A DRINKING FOUNTAIN IS REQUIRED. | | ALSO SEE SECTION 410.1 | | 2) IF TOILET ROOM ARE PROVIDED THEN EACH | | PUBLIC AND COMMON USE TOILET ROOM SHALL | | COMPLY WITH 11-4.22 - 11-4.1.3(11). | | THE FOLLOWING INFORMATION NOT SHOWN ON | | PLANS. 11-4.16.5 FLUSH CONTROLS, | | 11-4.19.2 HEIGHT & CLEARANCES, 11-4.19.3 | | CLEAR FLOOR SPACE, 11-4.19.4 EXPOSED | | PIPES AND SURFACES, 11-4.19.5 FAUCETS, | | AND 11-4.22.3 AN UNOBSTRUCTED TURNING | | SPACE. | | 3) NEW COMMENT: SHT 2, DOORS SHALL NOT | | SWING INTO THE CLEAR FLOOR SPACE REQUIR- | | ED FOR ANY FIXTURE. | | 4) NEW COMMENT: SEE ATTACHED SHEET FOR | | ENGINEER'S TITLE BLOCK. 61G15-23.002 | | 5) FLORIDA STATUTE 553.80(2)(B) | | SEE ATTACHED SHEET. - INFORMATIONAL | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|