Plan Review Notes
Plan Review Notes For Permit 03030708
Permit Number 03030708
Review Stop P
Sequence Number 1
Notes
Date Text
2003-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SUBMIT A SANITARY RISER DIAGRAM AND
 A WATER RISER DIAGRAM PER FBC ADMIN.
 CODE SEC. 104.3.1.1
 2) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 401.1
 3) IF TOILET ROOMS ARE PROVIDED THEN
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH 11-4.22. 11-4.1.3(11)
 PLEASE SUBMIT DETAILS FOR COMPLIANCE
 WITH 11-4.22 AND ALL SUBSECTIONS.
 4) IF BATHING ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE BATHROOM
 SHALL COMPLY WITH 11-4.23. 11-4.1.3(11)
 PLEASE SUBMIT DETAILS FOR 11-4.23 AND
 ALL SUBSECTIONS.
 5) BACKFLOW REQUIRED ON WATER SERVICE.
 6) PLEASE PROVIDE CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SEC'S
 1106 AND 1107. INCLUDE 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS. SHOW
 LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS, AND INDICATE SQUARE FOOTAGE
 DRAINED BY EACH,
 7) PROVIDE A STORM RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377