Plan Review Notes For Permit 03030708 |
Permit Number |
03030708 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-14 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | 1} SHOW SUB PANEL LOCATIONS FOR EACH OFF | | ICE. | | | | 2} PLEASE SHOW ALL CONTINUOUS AT | | 125%. (LIGHTING ETC) | | 215-2,215-3,230-42 | | | | 3} PLEASE LIST REQUIRED SIGN CIRCUITS PE | | R 600-5 | | | | 4} PLEASE SHOW HOW THE BATH RECEPTACLES | | COMPLY WITH 210-8(B).GFI. | | | | 5} PLEASE NOTE THAT PLANS ARE TO | | BE SIGNED, DATED AND SEALED BY AN P.E. | | PER FS/FAC 553-79-6A. | | | | 6} THE PANELS SHOWN ON THE RISER DIAGRAM | | DO NOT LIST THE OCP FOR THE FEEDERS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|