Plan Review Notes
Plan Review Notes For Permit 03030690
Permit Number 03030690
Review Stop P
Sequence Number 3
Notes
Date Text
2004-01-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) BATH #2 TUB AND WATER CLOSET ARE NOT
 VENTED, AND THERE IS NO LAV.
 B) BATH #1 HAS TWO FIXTURES, (IDENTIFI-
 ED AS SINKS), AND FLOOR PLAN SHOWS ONE
 LAV.
 C) CLEANOUT REQUIRED AT 4' ABOVE THE
 FLOOR ON WASH MACHINE STACK. 708.10
 D) WASH MACHINE REQUIRES A STANDPIPE
 PER 406.3
 E) ALL PIPES SHALL BE SIZED
 F) THE WASH MACHINE AND KITCHEN SINK
 ARE NEAR EACH OTHER ON THE FLOOR PLAN,
 BUT ON OPPOSITE SIDES OF THE HOUSE ON
 THE SANITARY RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]