Date |
Text |
2004-01-23 00:00:00 | ************** UNSAT ********** |
| |
| PLEASE SEE NOTE FROM FIRST TWO REVIEWS. |
| |
| 1)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| (B). PLANS REVIEWED WITH SAME COMMENTS |
| SUBJECT TO 4X FEE. |
| |
| 2)NOTE: PLEASE LIST THE REQUIRED DEDICAT |
| -ED BATH(S) CIRCUIT(S) PER 210.52D AND |
| 210.11C3. MUST BE SHOWN AS 20A AND #12 |
| |
| 3)NOTE: PLEASE STILL SEE NOTE ON RISER |
| THAT MENTIONS AND SHOWS OVERHEAD CONDUCT |
| -ORS FROM METER TO MAIN??? |
| |
| 4)NOTE: PLEASE SHOW LOCATION OF PANEL |
| ON PLANS. |
| |
| 5)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52 IN BEDROOMS AND MISSING RECEPT |
| FRONT OF DWELLING PER 210.52E |
| |
| 6)NOTE: PLEASE SEE PLANS, DO NOT SHOW |
| ELECTRICAL FOR WASHER/ DRYER/ WATER |
| HEATER??? DISC FOR WH?? |
| |
| 7)NOTE: PLAN NOTE MENTIONS DISC REQ'D |
| IF MORETHAN 8' BETWEEN METER AND PANEL. |
| PLEASE SEE LOCAL AMENDMENTS. NOTE IS |
| NOT CORRECT. |
| LOCAL AMENDMENTS: 230.70A. A MAIN IS |
| REQ'D ONLY WHEN THERE IS MORE THAN 8' |
| OF UNPROTECTED(OCP) CONDUCTORS"INSIDE" |
| THE BLDG. |
| IF THERE ARE ANY QUESTIONS ON THIS, |
| PLEASE CALL. |
| |
| 8)NOTE: PLEASE SEE LOAD SHOWN FOR A/C |
| COND UNIT. SHOWS 1200 VA?? |
| PLEASE ALSO VERIFY MAX OCP FOR 7.5 KW |
| MIN 125% (424.3) AND MAX 150%. |
| |
| 9)NOTE: PLEASE SHOW CONDUCTORS AND |
| POSSIBLE EQUIPMENT GRND ON LOAD SIDE |
| OF METER AND MAINDISC IF INSTALLED. |
| 250.110,250.24, 250.122 |
| |
| PLEASE ADDRESS ALL OF THE ABOVE COMMENTS |
| IF PLANS COME BACK AND ANY OF THE SAME |
| COMMENTS FROM PREVIOUS REVIEWS ARE NOT |
| DONE, THEN A 4X FEE WILL BE ACCESED. |
| PER FS 553.80(2)(B) ATTACHED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |