Plan Review Notes
Plan Review Notes For Permit 03030690
Permit Number 03030690
Review Stop E
Sequence Number 3
Notes
Date Text
2004-01-23 00:00:00************** UNSAT **********
  
 PLEASE SEE NOTE FROM FIRST TWO REVIEWS.
  
 1)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B). PLANS REVIEWED WITH SAME COMMENTS
 SUBJECT TO 4X FEE.
  
 2)NOTE: PLEASE LIST THE REQUIRED DEDICAT
 -ED BATH(S) CIRCUIT(S) PER 210.52D AND
 210.11C3. MUST BE SHOWN AS 20A AND #12
  
 3)NOTE: PLEASE STILL SEE NOTE ON RISER
 THAT MENTIONS AND SHOWS OVERHEAD CONDUCT
 -ORS FROM METER TO MAIN???
  
 4)NOTE: PLEASE SHOW LOCATION OF PANEL
 ON PLANS.
  
 5)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52 IN BEDROOMS AND MISSING RECEPT
 FRONT OF DWELLING PER 210.52E
  
 6)NOTE: PLEASE SEE PLANS, DO NOT SHOW
 ELECTRICAL FOR WASHER/ DRYER/ WATER
 HEATER??? DISC FOR WH??
  
 7)NOTE: PLAN NOTE MENTIONS DISC REQ'D
 IF MORETHAN 8' BETWEEN METER AND PANEL.
 PLEASE SEE LOCAL AMENDMENTS. NOTE IS
 NOT CORRECT.
 LOCAL AMENDMENTS: 230.70A. A MAIN IS
 REQ'D ONLY WHEN THERE IS MORE THAN 8'
 OF UNPROTECTED(OCP) CONDUCTORS"INSIDE"
 THE BLDG.
 IF THERE ARE ANY QUESTIONS ON THIS,
 PLEASE CALL.
  
 8)NOTE: PLEASE SEE LOAD SHOWN FOR A/C
 COND UNIT. SHOWS 1200 VA??
 PLEASE ALSO VERIFY MAX OCP FOR 7.5 KW
 MIN 125% (424.3) AND MAX 150%.
  
 9)NOTE: PLEASE SHOW CONDUCTORS AND
 POSSIBLE EQUIPMENT GRND ON LOAD SIDE
 OF METER AND MAINDISC IF INSTALLED.
 250.110,250.24, 250.122
  
 PLEASE ADDRESS ALL OF THE ABOVE COMMENTS
 IF PLANS COME BACK AND ANY OF THE SAME
 COMMENTS FROM PREVIOUS REVIEWS ARE NOT
 DONE, THEN A 4X FEE WILL BE ACCESED.
 PER FS 553.80(2)(B) ATTACHED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  