2003-11-25 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING REVISIONS TO
 THE PLAN FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE CLARIFY NOTE MENTIONING AND
 SHOWING OVERHEAD ELECTRIC THE METER AND
 THE DISCONNECT.
  
 3} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 4} MISSING SMOKE DETECTORS OUTSIDE OF
 TWO BEDROOMS.
  
 5} LIST BATH RECEPTACLES PER
 210.11(C)(3).#12,20 AMP.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.