Plan Review Notes For Permit 03030690 |
Permit Number |
03030690 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-11-25 00:00:00 | | | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE MAKE THE FOLLOWING REVISIONS TO | | THE PLAN FOR CODE COMPLIANCE AND | | RESUBMIT FOR REVIEW. | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} PLEASE CLARIFY NOTE MENTIONING AND | | SHOWING OVERHEAD ELECTRIC THE METER AND | | THE DISCONNECT. | | | | 3} PLEASE NOTE KITCHEN COUNTER- | | -SPACE RECEPT SPACING SHALL MEET ART; | | 210-52C 1,2,3,4,AND 5. | | | | 4} MISSING SMOKE DETECTORS OUTSIDE OF | | TWO BEDROOMS. | | | | 5} LIST BATH RECEPTACLES PER | | 210.11(C)(3).#12,20 AMP. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718. |
|