2003-12-05 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) THE OWNER/AGENT IS REQUIRED TO SIGN |
| THE ENERGY CALCULATION FORM. |
| |
| 4)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL WINDOW MULLIONS |
| - INSWING METAL DOOR (THE ONE SUBMITTED |
| IS FOR AN OUTSWING DOOR) |
| - SLIDING GLASS DOOR ( THE ONE SUBMITTED |
| IS NO LONGER VALID) SEE ATTACHED COPY OF |
| CURRENT NOA. |
| |
| 5) SUBMIT A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS OR APPLY |
| UNDER A SEPARATE PERMIT. HIGHLIGHT OR |
| CIRCLE THE TYPE OF MOUNTING AND ANCHORS |
| THAT WILL BE USED ON THE PRODUCT |
| APPROVAL. |
| |
| 6) REVISE THE WALL SECTION ON SHEET A1 |
| TO INDICATE THAT THE FINISH FLOOR IS A |
| MINIMUM OF 4" ABOVE FINAL GRADE AND THE |
| BOTTOM OF THE FOOTER IS REQUIRED TO BE A |
| MINIMUM OF 12" BELOW GRADE. SEE FBC |
| 1804.1.3 AND CITY OF WPB AMENDMENTS TO |
| FBC 1804.1.7. |
| |
| 7)1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREASES IN ALLOWABLE STRESS |
| SPECIFIED IN THE MATERIALS SECTIONS OF |
| THE CODE OR A REFRENCED STANDARD SHALL |
| NOT BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. REVISE THE TRUSS ANCHOR |
| UPLIFT VALUES LISTED ON A1 TO VALUES |
| THAT DO NOT INCLUDE A ONE THIRD STRESS |
| ON STEEL CALCULATIONS. SEE THE SIMPSON |
| HIGH WIND RESISTANT CONSTRUCTION CATALOG |
| SEE ATTACHED PAGE FROM CATALOG. |
| |
| 8) REVISE THE WINDOW/DOOR BUCK FASTENING |
| SCHEDULE ON A4. FBC 1707.4.4.2 REQUIRES |
| WINDOW AND DOOR ASSEMBLIES TO BE |
| FASTENED THROUGH THE 1X BUCKS AND INTO |
| THE STRUCTURAL SUBSTRATE. SEE NOTES ON |
| THE PLAN. |
| |
| PLEASE SEE NOTATIONS ON THE PLANS. |
| PLEASE RETURN OLD PLANS IN ORDER TO HELP |
| EXPEDITE PLAN REVIEW. |