2003-03-24 00:00:00************* UNSAT ****************
  
 1)NOTE : PLEASELIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. 210-12
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT. MAINS/BRKRS AND PANEL
 ARE TO BE RATED FOR THE AVAIALBE FAULT
 CURRENT.110-9
  
 3)NOTE: PLEASE CLARIFY NOTE, MENTIONING
 THAT OVERHEAD ELEC BETWEEN METERAND
 MAIN DISC?
  
 4)NOTE: PLEASE SEE PLANS, MISSING
 KITCHEN COUNTERSPACE RECEPTS PER
 210-52-C-1, ALSO WALL RECEPTS PER
 210-52. 2' OF WALL SPACE.
  
 5)NOTE: PLEASE SEE MISSING SD`S OUTSIDE
 TWO OF THE BEDROOMS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  