Plan Review Notes
Plan Review Notes For Permit 03030690
Permit Number 03030690
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-07 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) ENERGY CALCULATIONS ARE REQUIRED TO
 BE SIGNED AND DATED BY THE OWNER/AGENT.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOWS
 - STRUCTURAL MULLIONS
 - ROOFING MATERIALS
 - SLIDING GLASS DOORS
 - INSWING METAL DOOR
  
 5) THE CEILING AREA ON THE ENERGY CALCS.
 IS MORE THAN THE SQUARE FOOTAGE OF THE
 STRUCTURE AND NO TRAY OR VAULTED CEILING
 IS SHOWN ON THE PLANS. PLEASE CORRECT.
  
 6) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS OR A
 SEPARATE PERMIT AND FEES WILL BE
 REQUIRED.
  
 7) THE BOTTOM OF THE FOOTING IS REQUIRED
 TO BE A MINIMUM OF 12" BELOW FINISH
 GRADE PER FBC 1804.1.3.
  
 8) THE BUILDING FLOOR ELEVATION AT THE
 PERIMETER OF A MONOLITHIC FOUNDATION AT
 HABITABLE AREAS SHALL BE A MINIMUM OF 4"
 ABOVE FINISH GRADE PER CITY AMENDMENTS
 TO FBC 1804.1.7.
  
 9) INDICATE ON THE PLANS THAT THE WIRE
 MESH IN THE SLAB IS REQUIRED TO BE
 SUPPORTED ON APPROVED MATERIALS AT
 SPACINGS NOT TO EXCEED 3 FEET PER
 FBC 1909.3.
  
 10) UNDER THE WIND DESIGN PRESSURES ON
 A1, PRESSURES ARE LISTED FOR A GARAGE
 DOOR. THERE IS NO GARAGE ON THE PLANS.
 PLEASE CLARIFY.
  
 11) THE WALL SECTION ON A1 SPECS. 3- #5S
 IN THE FOOTING AND THE FOUNDATION PLAN
 SPECS. 2- #5S. PLEASE CORRECT.
  
 12) ON THE WALL SECTION ON A1, THE NAIL
 SPACING FOR THE ROOF SHEATHING IS LISTED
 FOR THE TIN TAG SPACING.
  
 13) THE SIMPSON HETA 20 CONNECTORS WITH
 8-10D X 1-1/2" NAILS SPECIFIED ON THE
 WALL SECTION ON A1 FOR THE HIP TRUSSES,
 WILL NOT PROVIDE THE REQUIRED 1820# OF
 UPLIFT RESISTANCE. SEE 2003 SIMPSON
 CATALOG. AN HETA 20 WITH 10-16D NAILS
 FOR A 2 PLY TRUSS IS RATED FOR 1890# OF
 UPLIFT. THE JOB SPECIFIC CONNECTOR
 SCHEDULE ON A3 REFERS TO CONNECTOR #7
 UNDER GENERAL NOTES FOR THE HIP TRUSSES.
 THIS IS A HETA 20 WITH 16-10D NAILS.
 PLEASE CLARIFY AND CORRECT.
  
 14) SHEET A3 UNDER SPECIAL NOTES SPECS.
 +37.1 PSF AS WORST CASE DESIGN PRESSURE
 FOR COMPONENTS AND CLADDING. WHAT IS THE
 NEGATIVE WORST CASE PRESSURE? THE WIND
 DESIGN PRESSURES ARE GIVEN AS +36 AND
 - 48 PSF ON A1. UNDER DESIGN PARAMETERS
 ON A1 COMPONENTS AND CLADDING DESIGN
 PRESSURES ARE LISTED AS +35.3 AND - 47.2
 PLEASE CORRECT.
  
 15) FBC 1707.4.4.2 REQUIRES WINDOW AND
 DOOR ASSEMBLIES TO BE FASTENED THROUGH
 1X BUCKS DIRECTLY TO THE STRUCTURAL
 SUBSTRATE. PLEASE REVISE WINDOW AND DOOR
 INSTALLATION CHART ON A4.
  
 16) INDICATE THE INTERNAL PRESSURE
 COEFFICENT UNDER DESIGN PARAMETERS ON
 A1. FOR AN ENCLOSED STRUCTURE IT IS
 + OR - 0.18.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202