Date |
Text |
2003-04-07 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) ENERGY CALCULATIONS ARE REQUIRED TO |
| BE SIGNED AND DATED BY THE OWNER/AGENT. |
| |
| 4)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SINGLE HUNG WINDOWS |
| - STRUCTURAL MULLIONS |
| - ROOFING MATERIALS |
| - SLIDING GLASS DOORS |
| - INSWING METAL DOOR |
| |
| 5) THE CEILING AREA ON THE ENERGY CALCS. |
| IS MORE THAN THE SQUARE FOOTAGE OF THE |
| STRUCTURE AND NO TRAY OR VAULTED CEILING |
| IS SHOWN ON THE PLANS. PLEASE CORRECT. |
| |
| 6) PROVIDE A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS OR A |
| SEPARATE PERMIT AND FEES WILL BE |
| REQUIRED. |
| |
| 7) THE BOTTOM OF THE FOOTING IS REQUIRED |
| TO BE A MINIMUM OF 12" BELOW FINISH |
| GRADE PER FBC 1804.1.3. |
| |
| 8) THE BUILDING FLOOR ELEVATION AT THE |
| PERIMETER OF A MONOLITHIC FOUNDATION AT |
| HABITABLE AREAS SHALL BE A MINIMUM OF 4" |
| ABOVE FINISH GRADE PER CITY AMENDMENTS |
| TO FBC 1804.1.7. |
| |
| 9) INDICATE ON THE PLANS THAT THE WIRE |
| MESH IN THE SLAB IS REQUIRED TO BE |
| SUPPORTED ON APPROVED MATERIALS AT |
| SPACINGS NOT TO EXCEED 3 FEET PER |
| FBC 1909.3. |
| |
| 10) UNDER THE WIND DESIGN PRESSURES ON |
| A1, PRESSURES ARE LISTED FOR A GARAGE |
| DOOR. THERE IS NO GARAGE ON THE PLANS. |
| PLEASE CLARIFY. |
| |
| 11) THE WALL SECTION ON A1 SPECS. 3- #5S |
| IN THE FOOTING AND THE FOUNDATION PLAN |
| SPECS. 2- #5S. PLEASE CORRECT. |
| |
| 12) ON THE WALL SECTION ON A1, THE NAIL |
| SPACING FOR THE ROOF SHEATHING IS LISTED |
| FOR THE TIN TAG SPACING. |
| |
| 13) THE SIMPSON HETA 20 CONNECTORS WITH |
| 8-10D X 1-1/2" NAILS SPECIFIED ON THE |
| WALL SECTION ON A1 FOR THE HIP TRUSSES, |
| WILL NOT PROVIDE THE REQUIRED 1820# OF |
| UPLIFT RESISTANCE. SEE 2003 SIMPSON |
| CATALOG. AN HETA 20 WITH 10-16D NAILS |
| FOR A 2 PLY TRUSS IS RATED FOR 1890# OF |
| UPLIFT. THE JOB SPECIFIC CONNECTOR |
| SCHEDULE ON A3 REFERS TO CONNECTOR #7 |
| UNDER GENERAL NOTES FOR THE HIP TRUSSES. |
| THIS IS A HETA 20 WITH 16-10D NAILS. |
| PLEASE CLARIFY AND CORRECT. |
| |
| 14) SHEET A3 UNDER SPECIAL NOTES SPECS. |
| +37.1 PSF AS WORST CASE DESIGN PRESSURE |
| FOR COMPONENTS AND CLADDING. WHAT IS THE |
| NEGATIVE WORST CASE PRESSURE? THE WIND |
| DESIGN PRESSURES ARE GIVEN AS +36 AND |
| - 48 PSF ON A1. UNDER DESIGN PARAMETERS |
| ON A1 COMPONENTS AND CLADDING DESIGN |
| PRESSURES ARE LISTED AS +35.3 AND - 47.2 |
| PLEASE CORRECT. |
| |
| 15) FBC 1707.4.4.2 REQUIRES WINDOW AND |
| DOOR ASSEMBLIES TO BE FASTENED THROUGH |
| 1X BUCKS DIRECTLY TO THE STRUCTURAL |
| SUBSTRATE. PLEASE REVISE WINDOW AND DOOR |
| INSTALLATION CHART ON A4. |
| |
| 16) INDICATE THE INTERNAL PRESSURE |
| COEFFICENT UNDER DESIGN PARAMETERS ON |
| A1. FOR AN ENCLOSED STRUCTURE IT IS |
| + OR - 0.18. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |