Plan Review Notes
Plan Review Notes For Permit 03030352
Permit Number 03030352
Review Stop E
Sequence Number 3
Notes
Date Text
2003-04-30 00:00:00************ UNSAT ******************
  
 PLEASE NOTE, NOW PLANS ARE BEING
 SUBMITTED SHOWING NEW RISER AS MENTIONED
 ON PREVIOUS PLANS. THE FOLLOWING ARE
 COMMENTS FOR NEW ELECTRICAL PLAN
 SUBMITTED.
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 PANELS, AND LOAD CALCUALTIONS. SOME
 SHOWN AS 100A AND OTHER AT 150A.
 PLEASE SHOW SERVICE/ PANEL(S) LOCATION
 ON PLANS.PLEASE NOTE, NOT MORE THAN 8'
 OF UNPROTECTED CONDUCTOR ARE PERMITTED
 INSIDE HOUSE .230-70/LOCAL AMENDMENTS
  
 2)NOTE: PLEASE REMOVE EQUIPMENT GROUND-
 -ING CONDUCTOR BETWEEN METER AND MAIN
 250-24
  
 3)NOTE: PLEASE CLARIFY AND SHOW NEW
 AND EXISTING LOAD CALCULATIONS COMBINE
 AS REQ`D IN ART 220/ 215-5. NEC
  
 4)NOTE: PLEASE CLARIFY NEW AND EXSITING
 HEAT FOR AHU`S. SHOWS 10KW AND 7.5KW.
  
 5)NOTE: PLEASE SEE MISSING RECEPT PER
 210-52 IN MASTER BEDROOM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SEE ATTACHED LETTER FOR PLANS
 PER FS 553.80(2)(B)