Plan Review Notes For Permit 03030352 |
Permit Number |
03030352 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-04-30 00:00:00 | ************ UNSAT ****************** | | | | PLEASE NOTE, NOW PLANS ARE BEING | | SUBMITTED SHOWING NEW RISER AS MENTIONED | | ON PREVIOUS PLANS. THE FOLLOWING ARE | | COMMENTS FOR NEW ELECTRICAL PLAN | | SUBMITTED. | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM, | | PANELS, AND LOAD CALCUALTIONS. SOME | | SHOWN AS 100A AND OTHER AT 150A. | | PLEASE SHOW SERVICE/ PANEL(S) LOCATION | | ON PLANS.PLEASE NOTE, NOT MORE THAN 8' | | OF UNPROTECTED CONDUCTOR ARE PERMITTED | | INSIDE HOUSE .230-70/LOCAL AMENDMENTS | | | | 2)NOTE: PLEASE REMOVE EQUIPMENT GROUND- | | -ING CONDUCTOR BETWEEN METER AND MAIN | | 250-24 | | | | 3)NOTE: PLEASE CLARIFY AND SHOW NEW | | AND EXISTING LOAD CALCULATIONS COMBINE | | AS REQ`D IN ART 220/ 215-5. NEC | | | | 4)NOTE: PLEASE CLARIFY NEW AND EXSITING | | HEAT FOR AHU`S. SHOWS 10KW AND 7.5KW. | | | | 5)NOTE: PLEASE SEE MISSING RECEPT PER | | 210-52 IN MASTER BEDROOM. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | | | PLEASE SEE ATTACHED LETTER FOR PLANS | | PER FS 553.80(2)(B) |
|