2003-04-02 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT ONE SET OF LOAD
 CALCULATIONS FOR NEW AND EXISTING.
  
 2)NOTE: PLEASE SEE NOTES, #11 MENTIONS
 NEW 150A SERVICE AND NO RISER DIAGRAM
 WAS SUBMITTED? PLEASE SUBMIT, SEC`S
 CONDUITS, AIC RATING FOR NEW MAIN/PANELS
 ETC. ETC. 215-5/110-9
  
 3)NOTE: PLEASE CLARIFY NEW OR EXSITING
 WATER HEATER AND LOAD? NOT SHOWN ON
 EXISTING OR NEW LOAD CALCS?
  
 4)NOTE: PLEASE RECONFIURE LOAD CALCS
 TO MEET NEC 220.
  
 5)NOTE: PLEASE SEE MISSING RECEPT PER
 210-52 ON WALL OUTSIDE BEDROOM. SITTING
 ROOM?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  