Plan Review Notes For Permit 03030326 |
Permit Number |
03030326 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-05-27 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) FROM PREVIOUS REVIEW: SHT A1, SHOWER | | SHALL COMPLY WITH SECTION 11-4.21 AND | | ALL SUBSECTIONS. NO DETAIL GIVEN FOR | | SECTIONS 11-4.21.5 (CONTROLS), 11-4.21.6 | | (SHOWER UNIT), 11-4.21.7 (CURB). PLEASE | | PROVIDE DETAILS. | | 2) FROM PREVIOUS REVIEW: SHT P-1, I | | ACKNOWLAGE RESPONSE FOR THE RELIEF VALVE | | FOR THERMAL EXPANSION PROTECTION, BUT | | A VACUUM RELIEF VALVE IS REQUIRED FOR | | ALL BOTTON FED WATER HEATERS PER SECTION | | 504.2 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|