Plan Review Notes
Plan Review Notes For Permit 03030326
Permit Number 03030326
Review Stop P
Sequence Number 2
Notes
Date Text
2003-05-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: SHT A1, SHOWER
 SHALL COMPLY WITH SECTION 11-4.21 AND
 ALL SUBSECTIONS. NO DETAIL GIVEN FOR
 SECTIONS 11-4.21.5 (CONTROLS), 11-4.21.6
 (SHOWER UNIT), 11-4.21.7 (CURB). PLEASE
 PROVIDE DETAILS.
 2) FROM PREVIOUS REVIEW: SHT P-1, I
 ACKNOWLAGE RESPONSE FOR THE RELIEF VALVE
 FOR THERMAL EXPANSION PROTECTION, BUT
 A VACUUM RELIEF VALVE IS REQUIRED FOR
 ALL BOTTON FED WATER HEATERS PER SECTION
 504.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692