Plan Review Notes For Permit 03030326
Permit Number 03030326
Review Stop P
Sequence Number 1
Notes
Date Text
2003-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A1, SHOWER SHALL COMPLY WITH
 SECTION 11-4.21 AND ALL SUBSECTIONS.
 PLEASE PROVIDE DETAILS.
 2) SHT P1 WATER HEATER DETAIL, THE
 RELIEF VALVE SHALL NOT BE USED AS A
 MEANS OF CONTROLLING THERMAL EXPANSION.
 SECTION 504.5. PLEASE SHOW EXPANSION
 TANK TO COMPLY WITH 607.3.2
 3) BACKFLOW PREVENTOR REQUIRED ON WATER
 SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377