Plan Review Notes For Permit 03030326 |
Permit Number |
03030326 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT A1, SHOWER SHALL COMPLY WITH | | SECTION 11-4.21 AND ALL SUBSECTIONS. | | PLEASE PROVIDE DETAILS. | | 2) SHT P1 WATER HEATER DETAIL, THE | | RELIEF VALVE SHALL NOT BE USED AS A | | MEANS OF CONTROLLING THERMAL EXPANSION. | | SECTION 504.5. PLEASE SHOW EXPANSION | | TANK TO COMPLY WITH 607.3.2 | | 3) BACKFLOW PREVENTOR REQUIRED ON WATER | | SERVICE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|