Plan Review Notes For Permit 03030326 |
Permit Number |
03030326 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-17 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE SEE TWO DIFFERENT AIC | | RATINGS FOR PANEL. RISER SHOWS 22K AND | | PANEL SHOWS 10K. PLEASE ALSO SUBMIT AIC | | RATING FOR NEW MAIN DISC PER 110-9. | | | | 2)NOTE; PLEASE CLARIFY LOAD CALCS, | | PLEASE SEE TWO DIFFERENT LOADS SHOWN? | | | | 3)NOTE: PLEASE CLARIFY USE OF MAINT BLDG | | AND ANY POSSIBLE LOCATIONS PER ART 500. | | 511? | | | | PLEASE NOTE, IT WAS REDLINED ONPLAN, | | AS PER LOCAL AMEDMENTS 215-5, FEEDERS | | FOR 277/480V ARE BROWN,PURPLE YELLOW(FYI | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|