Plan Review Notes
Plan Review Notes For Permit 03030326
Permit Number 03030326
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-17 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SEE TWO DIFFERENT AIC
 RATINGS FOR PANEL. RISER SHOWS 22K AND
 PANEL SHOWS 10K. PLEASE ALSO SUBMIT AIC
 RATING FOR NEW MAIN DISC PER 110-9.
  
 2)NOTE; PLEASE CLARIFY LOAD CALCS,
 PLEASE SEE TWO DIFFERENT LOADS SHOWN?
  
 3)NOTE: PLEASE CLARIFY USE OF MAINT BLDG
 AND ANY POSSIBLE LOCATIONS PER ART 500.
 511?
  
 PLEASE NOTE, IT WAS REDLINED ONPLAN,
 AS PER LOCAL AMEDMENTS 215-5, FEEDERS
 FOR 277/480V ARE BROWN,PURPLE YELLOW(FYI
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372