Plan Review Notes
Plan Review Notes For Permit 03030318
Permit Number 03030318
Review Stop P
Sequence Number 2
Notes
Date Text
2003-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 DRINKING FOUNTAIN DETAIL,
 PLEASE INDICATE SPOUT HEIGHT PER SECTION
 11-4.15.2.
 2) SHT A-3 DO ROOF DRAIN CALCULATIONS
 INCLUDE 1/2 AREA OF ALL VERTICAL WALLS
 AND AREA OF ANY ROOFS THAT DRAIN ON TO
 THE ROOF FROM ABOVE AS REQUESTED?
 3) SHT P-2 WATER HEATER DETAIL, SECTION
 504.2 VACUUM RELIEF HAS NOT BEEN ADDRESS
 ED. THERE ARE 3 TYPES OF VALVES REQD.
 4) SHTS P-2 & P-3 SERVICE SINK SHALL BE
 SHOWN ON PLUMBING PLANS AND SANITARY
 RISER DIAGRAM AND WATER RISER DIAGRAM TO
 REFLECT FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692