Plan Review Notes
Plan Review Notes For Permit 03030318
Permit Number 03030318
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A1 ENLARGED RESTROOM PLAN. LAV TO
 BE 1'3" OFF WALL. WATER CLOSET SHALL BE
 17" TO 19" MEASURED TO THE TOP OF THE
 TOILET SEAT. 11-4.16.3
 2) SHT A2 DETAIL #3, LAV TO BE 1'3" OFF
 WALL TO CENTER. BREAK ROOM (207) SINK
 TO COMPLY WITH 11-4.24 AND ALL SUBSECT-
 IONS. PLEASE SUBMIT DETAILS. - PLEASE
 SUBMIT DETAILS FOR DRINKING FOUNTAIN TO
 SHOW COMPLIANCE WITH 11-4.15 AND ALL SUB
 SECTIONS. SHOW CLEAR FLOOR SPACE.
 3) SHT A3 PROVIDE CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SEC'S.
 1106, & 1107. SHOW 1/2 AREA OF ALL VERT-
 ICAL WALLS INCLUDING PARAPETS. INCLUDE
 AREAS OF ALL ROOFS DRAINING FROM ABOVE.
 SHOW SIZE OF ALL OPENINGS FOR DOWNSPOUTS
 - SCUPPER
 SHOW SIZE OF ALL DOWNSPOUTS
 4) SHT P1 WILL THERE BE CHEMICALS STORED
 AND USED? IF SO MSDS SHEETS WILL BE REQD
 AND EMERGENCY SHOWER MAY BE REQUIRED DE-
 PENDING ON MSDS SHEETS.
 5) RPZ BACKFLOW REQUIRED ON BLDG WATER
 SERVOCE.
 6) SHT P2 WATER HEATER DETAIL. SECTION
 504.2 VACUUM RELIEF REQUIRED. SECTION
 607.3.2 THERMAL EXPANSION CONTROL REQD.'
 SECTION 504.5 THE RELIEF VALVE SHALL NOT
 BE USED AS MEANS OF THERMAL EXPANSION
 CONTROL.
 7) A SERVICE SINK IS REQUIRED PER TABLE
 403.1 (STORAGE)