Plan Review Notes
Plan Review Notes For Permit 03030306
Permit Number 03030306
Review Stop P
Sequence Number 2
Notes
Date Text
2003-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 WPB CITY CODE
  
 1) DO ROOF DRAIN CALCULATIONS INCLUDE
 1/2 AREA OF ALL VERTICAL WALLS AND ALL
 THE AREA OF THE ROOF THAT DRAINS ON TO
 THE ROOF FROM ABOVE? THIS INFORMATION IS
 NOT SHOWN AS REQUESTED.
 2) SHT A2.2 PROVIDE A DETAIL FOR THE
 SCUPPERS THAT COMPLY WITH SEC 1503.4.2
 2" MIN AND 4" MAX ABOVE ROOF TO FLOW
 LINE OF SCUPPER.
 3) SHT P-2 CONDENSATE SHALL NOT DRAIN IN
 TO SANITARY. CONDENSATE SHALL DRAIN TO
 THE EXTERIOR OF THE BLDG SEPARATELY AND
 SHALL TIE INTO THE STORM, A CATCH BASIN,
 OR DRYWELL MINIMUM OF 12" FROM THE BLDG.
 SECTION 1503.4.4. PLEASE PROVIDE DETAIL.
 -RESPONSE NOTED - CITY CODE SEC 90-125
 PROHIBITS CONDENSATE IN SANITARY SYSTEM.
 4) THE 5' TURNING RADIUS SHALL BE UN-
 OBSTRUCTED - THE DOOR SHALL NOT OPEN IN-
 TO THE TURNING RADIUS. SECTION 11-4.2.3
 THE SPACE FOR A WHEELCHAIR TO MAKE A 180
 DEGREE TURN IS A CLEAR SPACE OF 60"
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692