Plan Review Notes For Permit 03030306 |
Permit Number |
03030306 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-05-05 00:00:00 | PLEASE PROVIDE CONNECTION DETAILS OR | | FASTENING METHODS FOR THE "CAST STONE" | | TRIM SHOWN IN VARIOUS PLACES ON THE | | PLANS. | | SEE FBC 104.2. | | | | SHOW THE OPENING PROTECTIVES FOR THE | | LOUVERS IN THE EAST EXTERIOR WALL | | ELEVATION.SEE FBC 705.1.1.2. | | | | SECTION 3, SHEET A4.2 SHOWS FOAM | | MOLDINGWHICH IS PROHIBITTED BY FBC | | 102.2.7 AMENDED. | | | | PLEASE REVISE THE STRUCTURAL PLANS TO | | INCORPOATE THE SIX INCH BLOCK SPECIFIED | | ON SHEET A4.3.INCLUDE STRUCTURAL | | CALCLULATIONS. NOTE, THAT U906 | | INCORPORATES PROPRIETARY BLOCK. | | | | SHOW THE METHOD OF FIRE PROTECTION FOR | | THE SECOND FLOOR STRUCTURE.FBC | | 102.2.5. |
|