2003-03-26 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| |
| 1) PLEASE PROVIDE CALCULATIONS FOR MINI- |
| MUM FACILITIES. CONFERENCE ROOM AND MUL- |
| TI PURPOSE ROOM APPEAR TO B ASSEMBLY |
| WITHOUT FIXED SEATING, AND SHALL BE 7 |
| NET PER TABLE 1003.1 FBC-2001 |
| - AREA, NET FLOOR. THE AREA ACTUALLY |
| OCCUPIED NOT INCLUDING ACCESSORY UN- |
| OCCUPIED AREAS SUCH AS CORRIDORS, STAIRS |
| CLOSETS, THICKNESS OF WALLS, COLUMNS, |
| TOILET ROOM, MECHANICAL AREA OR OTHER |
| FEATURES. - |
| 2) TABLE 403.1 A DRINKING FOUNTAIN IS |
| REQUIRED. ALSO SEE SECTION 410.1 |
| 3) SHT A2.1 GROUND FLOOR PLAN AND DETAIL |
| #3, THE DOOR SHALL NOT OPEN INTO THE |
| 5' UNOBSTRUCTED TURNING CIRCLE. |
| 4) SHT A2.1 DETAIL #3 PLEASE SHOW CENTER |
| OF W/C OFF WALL TO BE 1'6" |
| 5) SHT A2.2 PLEASE PROVIDE CALCULATIONS |
| FOR PRIMARY AND SECONDARY ROOF DRAIN PER |
| SECTIONS 1106 & 1107. SHOW 1/2 AREA OF |
| ALL VERTICAL WALLS INCLUDING PARAPETS. |
| SHOW AREA OF ALL ROOF AREA THAT DRAINS |
| ON TO ROOF FROM ABOVE. - SCUPPER DETAIL |
| DOES NOT SHOW SIZE. PROVIDE HEIGHT AND |
| WIDTH. IF PRIMARY AND SECONDARY (SCUPPER |
| ARE DRAINING THROUGH THE SAME OPENING, |
| THEN THE OPENING PROVIDED SHALL BE LARGE |
| ENOUGH TO DRAIN THE AREA OF EACH. SHOW |
| SQUARE FOOTAGE DRAINED BY EACH OPENING. |
| INDICATE WHERE DOWNSPOUTS TERMINATE. |
| 6) SHT P1 SECTION 606.2 SHUTOFF VALVES |
| SHALL BE INSTALLED ON THE WATER SUPPLY |
| PIPE TO EACH SILLCOCK. |
| 7) SHT P2 CONDENSATE SHALL NOT DRAIN IN- |
| TO SANITARY. CONDENSATE SHALL DRAIN TO |
| THE EXTERIOR OF THE BLDG SEPARATELY AND |
| SHALL TIE INTO STORM, A CATCH BASIN, OR |
| DRYWELL, MINIMUM OF 12 FROM BLDG. PER |
| SECTION 1503.4.4 FBC-2001 PLEASE PROVIDE |
| DETAIL. |
| |
| REVIEW BY KEN STEVENS |