Plan Review Notes
Plan Review Notes For Permit 03030306
Permit Number 03030306
Review Stop P
Sequence Number 1
Notes
Date Text
2003-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE PROVIDE CALCULATIONS FOR MINI-
 MUM FACILITIES. CONFERENCE ROOM AND MUL-
 TI PURPOSE ROOM APPEAR TO B ASSEMBLY
 WITHOUT FIXED SEATING, AND SHALL BE 7
 NET PER TABLE 1003.1 FBC-2001
 - AREA, NET FLOOR. THE AREA ACTUALLY
 OCCUPIED NOT INCLUDING ACCESSORY UN-
 OCCUPIED AREAS SUCH AS CORRIDORS, STAIRS
 CLOSETS, THICKNESS OF WALLS, COLUMNS,
 TOILET ROOM, MECHANICAL AREA OR OTHER
 FEATURES. -
 2) TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. ALSO SEE SECTION 410.1
 3) SHT A2.1 GROUND FLOOR PLAN AND DETAIL
 #3, THE DOOR SHALL NOT OPEN INTO THE
 5' UNOBSTRUCTED TURNING CIRCLE.
 4) SHT A2.1 DETAIL #3 PLEASE SHOW CENTER
 OF W/C OFF WALL TO BE 1'6"
 5) SHT A2.2 PLEASE PROVIDE CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAIN PER
 SECTIONS 1106 & 1107. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS.
 SHOW AREA OF ALL ROOF AREA THAT DRAINS
 ON TO ROOF FROM ABOVE. - SCUPPER DETAIL
 DOES NOT SHOW SIZE. PROVIDE HEIGHT AND
 WIDTH. IF PRIMARY AND SECONDARY (SCUPPER
 ARE DRAINING THROUGH THE SAME OPENING,
 THEN THE OPENING PROVIDED SHALL BE LARGE
 ENOUGH TO DRAIN THE AREA OF EACH. SHOW
 SQUARE FOOTAGE DRAINED BY EACH OPENING.
 INDICATE WHERE DOWNSPOUTS TERMINATE.
 6) SHT P1 SECTION 606.2 SHUTOFF VALVES
 SHALL BE INSTALLED ON THE WATER SUPPLY
 PIPE TO EACH SILLCOCK.
 7) SHT P2 CONDENSATE SHALL NOT DRAIN IN-
 TO SANITARY. CONDENSATE SHALL DRAIN TO
 THE EXTERIOR OF THE BLDG SEPARATELY AND
 SHALL TIE INTO STORM, A CATCH BASIN, OR
 DRYWELL, MINIMUM OF 12 FROM BLDG. PER
 SECTION 1503.4.4 FBC-2001 PLEASE PROVIDE
 DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377