Plan Review Notes For Permit 03030306 |
Permit Number |
03030306 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-06 00:00:00 | 1) PLEASE BE ADVISED THAT THE BUILDING | | IS LOCATED IN THE CITY FIRE LIMITS. | | CERTAIN RESTRICTIONS APPLY. PLEASE | | SEE APPENDIX F OF THE LOCAL AMENDMENTS | | TO THE FLORIDA BUILDING CODE. | | | | 2) BUILDING ADDRESS REQUIRED ON PROPER | | ELEVATION. | | | | 3) PLEASE INDICATE INTERIOR FINISH | | FOR WALLS AND CEILINGS. | | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | FOR THE FIRE ALARM SYSTEM. | | | | 5) ALL MECHANICAL,ELECTRICAL,AND STORAGE | | ROOMS SHALL BE AT LEAST ONE HOUR | | FIRE RATED. OPENINGS IN THESE WALLS | | SHALL HAVE RATED FIRE DOORS. | | | | 6) ELEVATOR WARNING SIGNS REQUIRED. | | | | 7) TACTILE SIGNAGE REQUIRED DOORS | | ENTERING A STAIRWELL. | | | | 8) MORE DETAILS REQUIRED ON EGRESS DOOR | | PLANNED FOR THE FOLDING PARTITION. | | | | 9) PLEASE INDICATE HOW EXITING OCCURS | | FROM DOOR 110. PLANS SEEM TO SUGGEST | | A 4' HIGH OPAQUE WOOD FENCE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|