2003-03-06 00:00:00 | FAILED: |
| 1. CIVIL PLANS MUST BE SIGNED AND SEALED |
| BY THE CIVIL ENGINEER OF THE RECORD. |
| 2. A CLEAN-OUT NEED TO BE INSTALLED IN |
| THE SANITARY SEWER LATERAL, ON PROPERTY, |
| IMMEDIATELY AFTER CONNECTION TO SANITARY |
| SERVICE. |
| 3. PLEASE PROVIDE DRANAGE CALCULATION |
| FOR OUR REVIEW AND APPROVAL, SUBMITTALS |
| SHOULD INCLUDE CALCULATIONS FOR PERVIOUS |
| AND IMPERVIOUS FOR TOTAL SITE AND ALSO |
| THE TOTAL SITE AREA. |
| 4. DRIVEWAY APPROACHES MUS BE |
| CONSTRUCTED PER CITY' STANDARD AND |
| REQUIRMENTS. |
| 5.BACKFLOW PREVENTERS MUST BE COMPLETELY |
| HIDDEN FROM VIEW WITH SHRUBS PRIOR TO |
| ACTIVATION. |
| 6. SHEET C 1 SHOWS 5'X 4' EXFILTRATIONS |
| TRANCH, DETAIL ON SHEET C 2 SHOWS |
| 32'-8"3/16 X 19'-7"11/16 PLEASE VERIFY. |
| 7. TYPE C INLET SHOULD BE DETAILED PER |
| CITY' OR DOT STANDARD, PLEASE VERIFY THE |
| DIMENSIONS. |
| 8. CONCRETE SIDEWALK DETAILS SHOULD BE |
| REVISED TO FDOT STANDARD. |
| 9.COLORS OF PAINTS FOR PARKING STALLS |
| ARE NOT PER STANDARD, THEY SHOULD BE PER |
| CITY'S STANDARD OR PER FLORIDA |
| ACCESSIBILITY CODE. |
| 10. COMPACTED THICKNESSES FOR THE |
| PROPOSED PAVEMENT WITH BASE AND SUB-BASE |
| FOR THE PARKING AREA MUST BE SPECIFIED. |
| IF ANY QUESTION PLEASE CONTACT 659-8096 |