2003-03-06 00:00:00FAILED:
 1. CIVIL PLANS MUST BE SIGNED AND SEALED
 BY THE CIVIL ENGINEER OF THE RECORD.
 2. A CLEAN-OUT NEED TO BE INSTALLED IN
 THE SANITARY SEWER LATERAL, ON PROPERTY,
 IMMEDIATELY AFTER CONNECTION TO SANITARY
 SERVICE.
 3. PLEASE PROVIDE DRANAGE CALCULATION
 FOR OUR REVIEW AND APPROVAL, SUBMITTALS
 SHOULD INCLUDE CALCULATIONS FOR PERVIOUS
 AND IMPERVIOUS FOR TOTAL SITE AND ALSO
 THE TOTAL SITE AREA.
 4. DRIVEWAY APPROACHES MUS BE
 CONSTRUCTED PER CITY' STANDARD AND
 REQUIRMENTS.
 5.BACKFLOW PREVENTERS MUST BE COMPLETELY
 HIDDEN FROM VIEW WITH SHRUBS PRIOR TO
 ACTIVATION.
 6. SHEET C 1 SHOWS 5'X 4' EXFILTRATIONS
 TRANCH, DETAIL ON SHEET C 2 SHOWS
 32'-8"3/16 X 19'-7"11/16 PLEASE VERIFY.
 7. TYPE C INLET SHOULD BE DETAILED PER
 CITY' OR DOT STANDARD, PLEASE VERIFY THE
 DIMENSIONS.
 8. CONCRETE SIDEWALK DETAILS SHOULD BE
 REVISED TO FDOT STANDARD.
 9.COLORS OF PAINTS FOR PARKING STALLS
 ARE NOT PER STANDARD, THEY SHOULD BE PER
 CITY'S STANDARD OR PER FLORIDA
 ACCESSIBILITY CODE.
 10. COMPACTED THICKNESSES FOR THE
 PROPOSED PAVEMENT WITH BASE AND SUB-BASE
 FOR THE PARKING AREA MUST BE SPECIFIED.
 IF ANY QUESTION PLEASE CONTACT 659-8096