Plan Review Notes
Plan Review Notes For Permit 03030306
Permit Number 03030306
Review Stop B
Sequence Number 1
Notes
Date Text
2003-03-24 00:00:00THE PROPERTY SURVEY IS NOT SIGNED AND
 SEALED.
  
 SHEET A1 SHOWS THE PROPOSED BUILDING ON
 A SINGLE LOT 45' WIDE, THE SURVEY
 INDICATES TWO LOTS, ONE WITH AN
 EXISTING STRUCTURE.IF THE PROPERTIES
 ARE TO BE SEPARATE THE EAST WALL OF THE
 PROPOSED BUILDING MUST COMPLY WITH
 TABLE 600 FOR A WALL 5' FROM THE COMMON
 PROPERTY LINE.TWO STORY TYPE IV
 BUILDINGS IN THE DESIGNATED FIRE
 DISTRICT ARE REQUIRED BY FBC F102.2.6
 TO HAVE TWO HOUR RATED EXTERIOR WALLS.
 FBC F102.2.5 REQUIRES TWO STORY TYPE IV
 CONSTRUCTION TO BE ONE HOUR PROTECTED.
 PLEASE REVISE AS NECESSARY.
  
 SECTION 3, SHEET A4.2 SHOWS FOAM
 MOLDING. ARCHITECTURAL TRIM MUST COMPLY
 WITH FBC 102.2.7 AND BE NON-COMBUSTILE
 OR FIRE RETARDANT.
  
 THE WINDOWS AND DOOR IN THE EAST WALL
 ARE REQUIRED TO BE FIRE RATED.SEE FBC
 705.1.1.2.
  
 SHEET A2.2 DOES NOT INDICATE EMERGENCY
 OVERFLOW ROOF SCUPPERS.SEE FBC
 1511.6.4.3.
  
 SHEET S3 REFERENCES SSTD 12-97.THE FBC
 INVOKES SSTD 12-99, PLEASE REVISE AS
 NECESSARY AND ENSURE COMPLIANCE.SEE
 FBC 3502.
  
 NOTE 1 A ON SHEET S3 CALLS OUT AN
 INTERNAL PRESSURE COEFFICENT OF 0.55,
 WHICH DOES NOT APPEAR TO BE REFLECTED
 IN THE DECLARED NET ROOF UPLIFY OF 25
 PSF.
  
 THE FIRST FLOOR MULTI-PURPOSE ROOM AND
 THE SECOND FLOOR CONFERENCE ROOM ARE A2
 SMALL ASSEMBLY (>50 PERSONS) NOT GROUP
 B OCCUPANCY.SEE FBC 304.1.1.
  
 THE SECOND FLOOR REQUIRES TWO
 INDEPENDENT MEANS OF EGRESS.SEE FBC
 1004.1.2.
  
 FBC 1019.7.2 REQUIRES THE EXIT DOORS TO
 HAVE PANIC HARDWARE.
  
 SHEET C1 SHOWS THE FF ELEVATION AT
 20.5'AND THE IMMEDIATE SURROUNDING
 AREAS AT 19.0' - 19.4'HOW IS HANDICAP
 ACCESSIBILITY AT THE ENTRANCES/EXITS
 ACCOMPLISHED?