Plan Review Notes
Plan Review Notes For Permit 03030201
Permit Number 03030201
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-03 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE LOCATION AND SIZE OF THE
 ATTIC ACCESS TO THE AREA ABOVE THE
 MASTER BEDROOM.
  
 3) THE ROOF SHEATHING NAIL SPACING GIVEN
 ON SHEET GN1 IS INCORRECT. SEE CITY OF
 WPB AMENDMENTS TO THE FBC TABLE 2306.1.
  
 4) THE EXTERIOR STUCCO SOFFIT SPECS. #7
 ON A5 STATES THAT METAL LATH IS TO BE
 ATTACHED NOT MORE THAN 6" APART. ASTM C
 1063 REQUIRES 3/8" RIB METAL LATH TO BE
 ATTACHED AT EVERY RIB (4"O.C.). PLEASE
 REVISE.
  
 5) THE GIRDER AT THE SECOND FLOOR ABOVE
 BEDROOM #2 WITH AN UPLIFT OF 5455# AND
 BEARING ON THE (3) 2X6 HAS THE WRONG
 CONNECTOR SPECIFIED. SEE SHEET 3S. THE
 DETAIL THAT IS SPECIFIED SHOWS A USP
 USC 53 ATTACHED TO A MASONRY WALL.
 NOTE: SOME HOLDOWN STRAPS MAY NOT WORK
 AT THIS LOCATION DUE TO PROXIMITY TO THE
 CORNER.
  
 6) THE TRUSS/GIRDER CONNECTION DETAIL ON
 S3 SHOWS A 2X4 WALL. THE PLANS SHOW A
 2X6 WALL. PLEASE CORRECT.
  
 7) SPECIFY THE SPECIAL ROOF SHEATHING
 NAILING REQUIREMENTS REQUIRED BY CITY OF
 WPB AMENDMENTS TO FBC TABLE 2306.1.
 INDICATE THE FASTENER TYPES, SPACINGS
 AND ZONES ON THE PLANS.
  
 8) SPECIFY THE LENGTH OR EMBED DEPTH OF
 THE 1/2" DIA. EXPANSION ANCHORS AT THE
 WD. FRAME TO CONCRETE ATTACHMENT DETAIL
 ON A6.
  
 9) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORM.
  
 10) THE OPENING SIZES LISTED ON THE
 STORM PANEL SCHEDULE DO NOT MATCH THE
 WINDOW SIZES ON THE PLANS FOR NUMBERS 1,
 12, 15, 16, 18 AND 19. THE GLAZED FRENCH
 DOOR AT THE MASTER BEDROOM IS NOT SHOWN
 ON THE KEY PLAN OR SCHEDULE. THE SHUTTER
 WIDTH, HEIGHT AND SPAN ARE NOT GIVEN FOR
 OPENING #1. PLEASE CORRECT.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE GARAGE DOOR
 - SINGLE HUNG WINDOWS
 - GLAZED FRENCH DOOR AT MASTER BEDROOM
  
 12) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2.
  
 NOTE: PLEASE RETURN ALL OLD SHEETS OF
 DRAWINGS WHEN RESUBMITTING PLANS.