Date Text
2003-06-02 00:00:00UNSAT
 ~~~~~
 PLEASE PROVIDE A LOAD CALCULATION,RISER
 DIAGRAM AND PANEL SCHEDULE FOR ALL NEW
 EQUIPMENT.
  
 PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 NOTE THAT SMOKE DETECTORS ARE REQUIRED
 PER 8-1.4.2 NFPA-72,SHOW SAME ON PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718