Plan Review Notes For Permit 03030176 |
Permit Number |
03030176 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-06-02 00:00:00 | UNSAT | | ~~~~~ | | PLEASE PROVIDE A LOAD CALCULATION,RISER | | DIAGRAM AND PANEL SCHEDULE FOR ALL NEW | | EQUIPMENT. | | | | PLEASE LIST THE REQ'D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | NOTE THAT SMOKE DETECTORS ARE REQUIRED | | PER 8-1.4.2 NFPA-72,SHOW SAME ON PLANS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|