Plan Review Notes
Plan Review Notes For Permit 03030176
Permit Number 03030176
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-03 00:00:00**********CORRECTIONS************
  
 1.)BEFORE A PERMIT TO CONSTRUCT MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.THIS CAN BE DONE AT TIME
 OF ISSUANCE, AFTER THE PLANS HAVE BEEN
 APPROVED BUT BEFORE THE PERMIT IS
 PRINTED.
  
 2.)PROVIDE SOILS REPORT SHOWING
 BEARING CAPACITY.THIS MAY BE SUBMITTED
 LATER (AFTER PERMIT ISSUANCE).
  
 3.)FILE A NOTICE OF COMMENCEMENT WITH
 THE CLERK'S OFFICE.BRING A RECORDED
 CERTIFIED COPY TO THIS OFFICE.THIS
 MUST BE DONE BEFORE THE PERMIT CAN BE
 PICKED UP.
  
 4.)PER FBC 1814.3.3, DAMPPROOFING
 IS REQUIRED TO BE .006.PLEASE REVISE
 NOTES #1.
  
 5.) HURRICANE PROTECTION REQUIRED FOR
 WINDOWS.ANY OF THE FOLLOWING OPTIONS
 WOULD BE ACCEPTABLE:
  
 A.) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR SHUTTERS, OR
 B.) WINDOWS TO BE IMPACT GLASS,
 CHANGE PLAN AND SUBMIT PRODUCT
 APPROVALS, OR
 C.) INDICATE ON PLAN THAT SHUTTERS
 ARE REQUIRED, BUT A PERMIT
 CAN BE APPLIED FOR LATER.
  
 6.) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7.)PROVIDE WINDOW SIZES FOR THE
 WINDOWS IN THE ADDITION.
  
 8.)2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.PLEASE HAVE THE BEDROOM
 EGRESS WINDOW INDICATED ON THE PLAN.
  
 9.)WHEN CHANGES ARE MADE TO A SEALED
 DRAWING, THEY ARE TO BE MADE BY THE
 ARCHITECT OR ENGINEER ONLY, AND THOSE
 CHANGES SHOULD BE INITIALED.THE CHANGE
 IN INK (NOT INITIALED) FOR THE WOOD
 DOOR TO BE A METAL DOOR SHOULD BE
 INITIALED, AND THE FLOOR PLAN CHANGED
 AS WELL.
  
 10.)FIREBLOCKING REQUIRED PER FBC
 2305.1.PLEASE REVISE WALL SECTION.
  
 11.)WALL SECTION MUST SPECIFY WHICH
 HURRICANE STRAPS ARE TO BE USED, EITHER
 BY NAMING A BRAND AND TYPE OF STRAP TO
 BE USED, OR BY SPECIFYING UPLIFT
 REQUIREMENTS FOR THE STRAP.
  
 12.)FOOTER DEPTH REQUIRED TO BE
 16" MIN. PER CITY AMENDMENTS TO THE FBC
 1804.1.7.
  
 13.)PROVIDE A SHEATHING NAILING
 SCHEDULE.PLEASE NOTE CITY AMENDMENTS
 2306.1 REVISED TABLE.
  
 14.)THE FLOOR PLAN SHOWS A SINGLE
 WINDOW OF 6'2, BUT THE PRODUCT APPROVALS
 SUBMITTED SHOWS A MAX WIDTH OF 52".
 IF THIS IS TO BE TWO WINDOWS MULLED
 TOGETER, CHANGE THE PLAN TO INDICATE
 THIS AND PROVIDE PRODUCT APPROVALS FOR
 THE MULLIONS.IF THIS IS TO BE ONE
 WINDOW, PROVIDE PRODUCT APPROVALS FOR
 THE WINDOW YOU PLAN TO INSTALL IN THIS
 LOCATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724