2003-04-03 00:00:00 | **********CORRECTIONS************ |
| |
| 1.)BEFORE A PERMIT TO CONSTRUCT MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION.THIS CAN BE DONE AT TIME |
| OF ISSUANCE, AFTER THE PLANS HAVE BEEN |
| APPROVED BUT BEFORE THE PERMIT IS |
| PRINTED. |
| |
| 2.)PROVIDE SOILS REPORT SHOWING |
| BEARING CAPACITY.THIS MAY BE SUBMITTED |
| LATER (AFTER PERMIT ISSUANCE). |
| |
| 3.)FILE A NOTICE OF COMMENCEMENT WITH |
| THE CLERK'S OFFICE.BRING A RECORDED |
| CERTIFIED COPY TO THIS OFFICE.THIS |
| MUST BE DONE BEFORE THE PERMIT CAN BE |
| PICKED UP. |
| |
| 4.)PER FBC 1814.3.3, DAMPPROOFING |
| IS REQUIRED TO BE .006.PLEASE REVISE |
| NOTES #1. |
| |
| 5.) HURRICANE PROTECTION REQUIRED FOR |
| WINDOWS.ANY OF THE FOLLOWING OPTIONS |
| WOULD BE ACCEPTABLE: |
| |
| A.) SUBMIT TWO COPIES OF PRODUCT |
| APPROVALS FOR SHUTTERS, OR |
| B.) WINDOWS TO BE IMPACT GLASS, |
| CHANGE PLAN AND SUBMIT PRODUCT |
| APPROVALS, OR |
| C.) INDICATE ON PLAN THAT SHUTTERS |
| ARE REQUIRED, BUT A PERMIT |
| CAN BE APPLIED FOR LATER. |
| |
| 6.) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 7.)PROVIDE WINDOW SIZES FOR THE |
| WINDOWS IN THE ADDITION. |
| |
| 8.)2001 FL BLD CODE, 1005.4: |
| PROVIDE EMERGENCY EGRESS WINDOWS IN |
| SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| OPENING HEIGTH OF 24" AND NET CLEAR |
| OPENING WIDTH OF 20" AND A NET CLEAR |
| OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| OPENINGS ARE PERMITTED TO HAVE A NET |
| CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| SHALL NOT BE MORE THAN 44 " ABOVE THE |
| FINISH FLOOR.PLEASE HAVE THE BEDROOM |
| EGRESS WINDOW INDICATED ON THE PLAN. |
| |
| 9.)WHEN CHANGES ARE MADE TO A SEALED |
| DRAWING, THEY ARE TO BE MADE BY THE |
| ARCHITECT OR ENGINEER ONLY, AND THOSE |
| CHANGES SHOULD BE INITIALED.THE CHANGE |
| IN INK (NOT INITIALED) FOR THE WOOD |
| DOOR TO BE A METAL DOOR SHOULD BE |
| INITIALED, AND THE FLOOR PLAN CHANGED |
| AS WELL. |
| |
| 10.)FIREBLOCKING REQUIRED PER FBC |
| 2305.1.PLEASE REVISE WALL SECTION. |
| |
| 11.)WALL SECTION MUST SPECIFY WHICH |
| HURRICANE STRAPS ARE TO BE USED, EITHER |
| BY NAMING A BRAND AND TYPE OF STRAP TO |
| BE USED, OR BY SPECIFYING UPLIFT |
| REQUIREMENTS FOR THE STRAP. |
| |
| 12.)FOOTER DEPTH REQUIRED TO BE |
| 16" MIN. PER CITY AMENDMENTS TO THE FBC |
| 1804.1.7. |
| |
| 13.)PROVIDE A SHEATHING NAILING |
| SCHEDULE.PLEASE NOTE CITY AMENDMENTS |
| 2306.1 REVISED TABLE. |
| |
| 14.)THE FLOOR PLAN SHOWS A SINGLE |
| WINDOW OF 6'2, BUT THE PRODUCT APPROVALS |
| SUBMITTED SHOWS A MAX WIDTH OF 52". |
| IF THIS IS TO BE TWO WINDOWS MULLED |
| TOGETER, CHANGE THE PLAN TO INDICATE |
| THIS AND PROVIDE PRODUCT APPROVALS FOR |
| THE MULLIONS.IF THIS IS TO BE ONE |
| WINDOW, PROVIDE PRODUCT APPROVALS FOR |
| THE WINDOW YOU PLAN TO INSTALL IN THIS |
| LOCATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |