2003-05-01 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| MODEL D (REVERSE) |
| |
| 1) SHEET S-1, ROOF FRAMING PLAN.THE |
| ROOF TRUSS ANCHOR AT THE WALL BETWEEN |
| THE ATRIUM AND BEDROOM 2 IS CALLED UP AS |
| DETAIL 5/S-4. SHEET S-4 HAS NO DETAIL 5. |
| AMEND THE PLANS TO CORRELATE THE DETAILS |
| IF THE REFERENCE ON THE ROOF FRAMING |
| PLAN SHOULD BE TO DETAIL 4/S-4, AS DRAWN |
| ON SHEET S-4, THEN THE COPIES OF |
| SHEET S-1 MAY BE HAND-CORRECTED BY THE |
| ENGINEER OF RECORD.SUCH A CORRECTION |
| SHALL BE SIGNED AND DATED BY THE |
| ENGINEER. |
| |
| 2) SHEET S-1, ROOF FRAMING PLAN.THE |
| HIP JACK ANCHOR AT THE PATIO COLUMN IS |
| CALLED UP AS CONNECTOR MARK 8.THE |
| CONNECTOR SCHEDULE ON S-2 DOES NOT |
| INCLUDE A MARK 8.AMEND THE PLANS. |
| |
| 3) NOTE: IF SHEET S-2 IS TO BE AMENDED, |
| PLEASE CORRECT THE CONNECTOR MARK 4 |
| (SIMPSON MGT) ALLOWABLE UPLIFT TO 3965# |
| (CURRENTLY SHOWN AS 4200#). |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |