Notes |
Date |
Text |
2003-08-19 00:00:00 | **************** UNSAT ************ | | | | PLEASE SEE THAT A CO HAS BEEN ISSUED ON | | THIS PROPERTY AS OF 8/18/03. I HAVE SENT | | NOTICE TO THE CHIEF BLDG INSPECTOR TO | | REVOKE/HOLD CO UNTIL ALL PLANS HAVE BEEN | | CLEARED UP. | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF | | FAC 61G15-23.002/ FS 471 FOR ALL | | INFORMATION REQ'D ON TITLE BLOCK OF | | PLANS FOR EACH PLAN. | | EACH PLAN IS TO INCLUDE ADDRESS/LOT # | | OF JOB. | | | | 2)NOTE: PLEASE VERFIY SERVICE SHOWN ON | | RISER DIAGRAM WITH ACTUAL FIELD INSTALL- | | -ATION. | | RISER DIAGRAM SHOWS A 200A METER/MAIN | | COMBO FEEDING A 150A MAIN DISC AND THEN | | FEEDING A 150A MCB PANEL ON THE INTERIOR | | ????? | | PLEASE ALSO SEE NO CONDUCTOR SIZE SHOWN | | FROM METER/MAIN TO 150A DISC.?? | | 150A DISC MAY NOT BE FED FROM A 200A | | MAIN. 240 ETC. | | PLEASE ALSO SEE PLAN, DOES NOT SHOW | | ADDITIONAL MAIN ON OUTSIDE OF GARAGE.? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. PLEASE CORRELATE WITH FIELD | | INSTALLATION. | | CO WILL BE ON HOLD OR REVOKED UNTILL | | PLANS ARE CORRECTED. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|