Plan Review Notes
Plan Review Notes For Permit 03030015
Permit Number 03030015
Review Stop E
Sequence Number 3
Notes
Date Text
2003-08-19 00:00:00**************** UNSAT ************
  
 PLEASE SEE THAT A CO HAS BEEN ISSUED ON
 THIS PROPERTY AS OF 8/18/03. I HAVE SENT
 NOTICE TO THE CHIEF BLDG INSPECTOR TO
 REVOKE/HOLD CO UNTIL ALL PLANS HAVE BEEN
 CLEARED UP.
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF
 FAC 61G15-23.002/ FS 471 FOR ALL
 INFORMATION REQ'D ON TITLE BLOCK OF
 PLANS FOR EACH PLAN.
 EACH PLAN IS TO INCLUDE ADDRESS/LOT #
 OF JOB.
  
 2)NOTE: PLEASE VERFIY SERVICE SHOWN ON
 RISER DIAGRAM WITH ACTUAL FIELD INSTALL-
 -ATION.
 RISER DIAGRAM SHOWS A 200A METER/MAIN
 COMBO FEEDING A 150A MAIN DISC AND THEN
 FEEDING A 150A MCB PANEL ON THE INTERIOR
 ?????
 PLEASE ALSO SEE NO CONDUCTOR SIZE SHOWN
 FROM METER/MAIN TO 150A DISC.??
 150A DISC MAY NOT BE FED FROM A 200A
 MAIN. 240 ETC.
 PLEASE ALSO SEE PLAN, DOES NOT SHOW
 ADDITIONAL MAIN ON OUTSIDE OF GARAGE.?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE CORRELATE WITH FIELD
 INSTALLATION.
 CO WILL BE ON HOLD OR REVOKED UNTILL
 PLANS ARE CORRECTED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]